TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
REVISION OF KPLC STANDARDS
To keep abreast of progress in the industry, KPLC Standards shall be regularly reviewed. Suggestions for improvements to approved Standards, addressed to the Manager, Standards department, are welcome.| REVISION OF KPLC STANDARDS |
| :--- |
| To keep abreast of progress in the industry, KPLC Standards shall be regularly reviewed. Suggestions for improvements to approved Standards, addressed to the Manager, Standards department, are welcome. |
Kenya Power & Lighting Company Plc
Users are reminded that by virtue of Section 25 of the Copyright Act, 2001 (Revised 2009) Cap 130 of the Laws of Kenya, copyright subsists in all KPLC standards and except as provided under Section 26 of this Act, no KPLC standard produced by KPLC may be reproduced, stored in retrieval system by any means without prior permission from the Managing Director & CEO, KPLC| Kenya Power & Lighting Company Plc |
| :--- |
| Users are reminded that by virtue of Section 25 of the Copyright Act, 2001 (Revised 2009) Cap 130 of the Laws of Kenya, copyright subsists in all KPLC standards and except as provided under Section 26 of this Act, no KPLC standard produced by KPLC may be reproduced, stored in retrieval system by any means without prior permission from the Managing Director & CEO, KPLC |
发布者标准制定科科长
授权人:标准部主任
已签署:
已签署:
日期:2023-91-24
日期: 2023-01-24
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No_(+) 7
Revision No. 0
Date of Issue 2023-01-24
Page 3 of 50
0.1 Circulation List
"COPY NO.
COPY HOLDER
l
Standards Manager
2
Electronic copy (pdf) on KPLC server currently: http://172.16.1.40/dms/browse.php?fFolderId=23"
"REVISION OF KPLC STANDARDS
To keep abreast of progress in the industry, KPLC Standards shall be regularly reviewed. Suggestions for improvements to approved Standards, addressed to the Manager, Standards department, are welcome."
"Kenya Power & Lighting Company Plc
Users are reminded that by virtue of Section 25 of the Copyright Act, 2001 (Revised 2009) Cap 130 of the Laws of Kenya, copyright subsists in all KPLC standards and except as provided under Section 26 of this Act, no KPLC standard produced by KPLC may be reproduced, stored in retrieval system by any means without prior permission from the Managing Director & CEO, KPLC"
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023-91-24 Date: 2023-01-24 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- | :--- |
| | | | Issue $\mathrm{No}_{+}$ | 7 |
| | | | Revision No. | 0 |
| | | | Date of Issue | 2023-01-24 |
| | | | Page 3 of 50 | |
| 0.1 Circulation List | | | | |
| COPY NO. <br> COPY HOLDER <br> l <br> Standards Manager <br> 2 <br> Electronic copy (pdf) on KPLC server currently: http://172.16.1.40/dms/browse.php?fFolderId=23 | | | | |
| | | | | | | |
| | | | | | | |
| REVISION OF KPLC STANDARDS <br> To keep abreast of progress in the industry, KPLC Standards shall be regularly reviewed. Suggestions for improvements to approved Standards, addressed to the Manager, Standards department, are welcome. | | | | |
| Kenya Power & Lighting Company Plc <br> Users are reminded that by virtue of Section 25 of the Copyright Act, 2001 (Revised 2009) Cap 130 of the Laws of Kenya, copyright subsists in all KPLC standards and except as provided under Section 26 of this Act, no KPLC standard produced by KPLC may be reproduced, stored in retrieval system by any means without prior permission from the Managing Director & CEO, KPLC | | | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | | |
| Signed: | | Signed: | | |
| Date: 2023-91-24 | | Date: 2023-01-24 | | |
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KPI/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 4 页,共 50 页
0.2 修正记录
修订
日期
变化说明
编制人
批准编号 (YYYY-MM-DD)
第 7 期
2023-01-24
取消并取代第 6 期修订版 1
M.基马蒂
Eng.彼得以及之前的所有问题。
F.Gicugu Kimemia
S.恩古利
B.King'esi
J.金达
G. 韦利莫
J.恩迪兰古
J.Ng'ang'a
4.4.2
卷绕
返回铝材。
4.4.2.2
中学
铝制绕组应由绕组铝条制成。
4.5.2.2
轻触开关
外部手轮的材料应为耐腐蚀金属。
4.6.2.2
工作助焊剂
密度不得超过 1.7 特斯拉。
4.7.1
短路
短路阻抗应符合表 5 阻抗和 IEC 60076-1 规定的适用公差。
4.9.1.12
衬套杆和 13
指定为黄铜。指定当前容量和尺寸。
4.15
避雷器
4.16 .1
压力
它不得突出于高压套管之外。 降压装置
泄压装置的大小应能防止罐体超压。
4.16.1 f
夹钳
锡涂层厚度应为 25 mum25 \mu \mathrm{~m} 。 连接器
Rev
Date
Description of Change
Prepared by
Approved by No. (YYYY-MM-DD)
Issue 7
2023-01-24
Cancels & replaces Issue 6 Rev 1
M. Kimathi
Dr. Eng. Peter and all previous issues.
F. Gicugu Kimemia
S. Nguli
B. King'esi
J. Kinda
G. Welimo
J. Ndirangu
J. Ng'ang'a
4.4.2
Winding
Aluminum returned.
4.4.2.2
Secondary
The aluminium winding shall be made of a strip of winding aluminium.
4.5.2.2
Tap switch
The material of the external hand wheel shall be a corrosion resistant metal.
4.6.2.2
Working flux
Shall not exceed 1.7 Tesla. density
4.7.1
Short circuit
The short circuit impedance shall be as given in table 5 impedance and applicable tolerances as per IEC 60076-1.
4.9.1.12
Bushing rod & 13
Specified as brass. Current capacity and size specified. material
4.15
Surge arrester
4.16 .1
Pressure
It shall not protrude beyond the HV bushings. relief device
The pressure relief device shall be sized to protect the tank against overpressure.
4.16.1 f
Clamp
Tin coating thickness shall be 25 mum. connector| Rev |
| :--- |
| Date |
| Description of Change |
| Prepared by |
| Approved by No. (YYYY-MM-DD) |
| Issue 7 |
| 2023-01-24 |
| Cancels & replaces Issue 6 Rev 1 |
| M. Kimathi |
| Dr. Eng. Peter and all previous issues. |
| F. Gicugu Kimemia |
| S. Nguli |
| B. King'esi |
| J. Kinda |
| G. Welimo |
| J. Ndirangu |
| J. Ng'ang'a |
| 4.4.2 |
| Winding |
| Aluminum returned. |
| 4.4.2.2 |
| Secondary |
| The aluminium winding shall be made of a strip of winding aluminium. |
| 4.5.2.2 |
| Tap switch |
| The material of the external hand wheel shall be a corrosion resistant metal. |
| 4.6.2.2 |
| Working flux |
| Shall not exceed 1.7 Tesla. density |
| 4.7.1 |
| Short circuit |
| The short circuit impedance shall be as given in table 5 impedance and applicable tolerances as per IEC 60076-1. |
| 4.9.1.12 |
| Bushing rod & 13 |
| Specified as brass. Current capacity and size specified. material |
| 4.15 |
| Surge arrester |
| 4.16 .1 |
| Pressure |
| It shall not protrude beyond the HV bushings. relief device |
| The pressure relief device shall be sized to protect the tank against overpressure. |
| 4.16.1 f |
| Clamp |
| Tin coating thickness shall be $25 \mu \mathrm{~m}$. connector |
发布者标准制定科科长
授权人:标准部主任
已签署:
已签署:
日期: 2023-01-24
日期: 2023-01-24
"TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KPI/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 4 of 50
0.2 Amendment Record
"Rev
Date
Description of Change
Prepared by
Approved by No. (YYYY-MM-DD)
Issue 7
2023-01-24
Cancels & replaces Issue 6 Rev 1
M. Kimathi
Dr. Eng. Peter and all previous issues.
F. Gicugu Kimemia
S. Nguli
B. King'esi
J. Kinda
G. Welimo
J. Ndirangu
J. Ng'ang'a
4.4.2
Winding
Aluminum returned.
4.4.2.2
Secondary
The aluminium winding shall be made of a strip of winding aluminium.
4.5.2.2
Tap switch
The material of the external hand wheel shall be a corrosion resistant metal.
4.6.2.2
Working flux
Shall not exceed 1.7 Tesla. density
4.7.1
Short circuit
The short circuit impedance shall be as given in table 5 impedance and applicable tolerances as per IEC 60076-1.
4.9.1.12
Bushing rod & 13
Specified as brass. Current capacity and size specified. material
4.15
Surge arrester
4.16 .1
Pressure
It shall not protrude beyond the HV bushings. relief device
The pressure relief device shall be sized to protect the tank against overpressure.
4.16.1 f
Clamp
Tin coating thickness shall be 25 mum. connector"
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023-01-24 Date: 2023-01-24 | | | | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | | Doc. No. | | KPI/13D/13/TSP/10/001-02 | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | | | Issue No. | 7 | | |
| | | | Revision No. | 0 | | |
| | | | Date of Issue | | 2023-01-24 | |
| | | | Page 4 of 50 | | | |
| 0.2 Amendment Record | | | | | | | | | |
| Rev <br> Date <br> Description of Change <br> Prepared by <br> Approved by No. (YYYY-MM-DD) <br> Issue 7 <br> 2023-01-24 <br> Cancels & replaces Issue 6 Rev 1 <br> M. Kimathi <br> Dr. Eng. Peter and all previous issues. <br> F. Gicugu Kimemia <br> S. Nguli <br> B. King'esi <br> J. Kinda <br> G. Welimo <br> J. Ndirangu <br> J. Ng'ang'a <br> 4.4.2 <br> Winding <br> Aluminum returned. <br> 4.4.2.2 <br> Secondary <br> The aluminium winding shall be made of a strip of winding aluminium. <br> 4.5.2.2 <br> Tap switch <br> The material of the external hand wheel shall be a corrosion resistant metal. <br> 4.6.2.2 <br> Working flux <br> Shall not exceed 1.7 Tesla. density <br> 4.7.1 <br> Short circuit <br> The short circuit impedance shall be as given in table 5 impedance and applicable tolerances as per IEC 60076-1. <br> 4.9.1.12 <br> Bushing rod & 13 <br> Specified as brass. Current capacity and size specified. material <br> 4.15 <br> Surge arrester <br> 4.16 .1 <br> Pressure <br> It shall not protrude beyond the HV bushings. relief device <br> The pressure relief device shall be sized to protect the tank against overpressure. <br> 4.16.1 f <br> Clamp <br> Tin coating thickness shall be $25 \mu \mathrm{~m}$. connector | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| Issued by: Head of Section, Standard development | | | | | Authorized by: Head of Department, Standards | | | | |
| Signed: | | | | | Signed: | | | | |
| Date: 2023-01-24 | | | | | Date: 2023-01-24 | | | | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KPL/13D/13/TSP/10/001-02
问题编号 .
7
修订编号
0
发行日期
2023-01-24
第 5 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KPL/13D/13/TSP/10/001-02
Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 5 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KPL/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No . | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 5 of 50 | |
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Sudys Signed:
Date: 2023-01-24 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: Sudys | Signed: |
| Date: $2023-01-24$ | Date: 2023-01-24 |
肯尼亚电力公司
标题: 配电变压器 Patt 2:杆装三相油式配电变压器 - 规格
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 6 页,共 50 页
2.参考文献 下列标准所包含的条款通过在本文中引用而构成本规范的条款。除非另有说明,本规范适用最新版本(包括修订版)。除非另有说明,否则适用最新版本(包括修订版)。ISO 1461: {:[" 1461: "," Hot dip galvanized "],[," Specifications and test methods. "]:}\begin{array}{ll}\text { 1461: } & \text { Hot dip galvanized } \\ & \text { Specifications and test methods. }\end{array} 钢铁制品上的热浸镀锌层 规格和试验方法。
2. REFERENCES
The following standards contain provisions which, through reference in this text constitute provisions
this Specification. Unless otherwise stated, the latest editions (including amendments) apply. of this Specification. Unless otherwise stated, the latest editions (including amendments) apply. ISO 1461: 1461:, Hot dip galvanized, , Specifications and test methods.
Hot dip galvanized coatings on fabricated iron and steel articles Specifications and test methods.| 2. REFERENCES |
| :--- |
| The following standards contain provisions which, through reference in this text constitute provisions |
| this Specification. Unless otherwise stated, the latest editions (including amendments) apply. of this Specification. Unless otherwise stated, the latest editions (including amendments) apply. ISO 1461: $\begin{array}{ll}\text { 1461: } & \text { Hot dip galvanized } \\ & \text { Specifications and test methods. }\end{array}$ |
| Hot dip galvanized coatings on fabricated iron and steel articles Specifications and test methods. |
IEC 60076-1, 2, 3,
Power transformers - Part 1: General; -Part 2: Temperature rise; 4, 5, 7&10: Part 3: Insulation levels dielectric tests and external air clearances; - Part 4: Guide to the lightning impulse testing- power transformers and reactors; - Part 5: Ability to withstand short circuit;- Part 7: Loading guide for oil immersed power transformers - Part 10: Determination of sound levels.| IEC 60076-1, 2, 3, |
| :--- |
| Power transformers - Part 1: General; -Part 2: Temperature rise; 4, 5, 7&10: Part 3: Insulation levels dielectric tests and external air clearances; - Part 4: Guide to the lightning impulse testing- power transformers and reactors; - Part 5: Ability to withstand short circuit;- Part 7: Loading guide for oil immersed power transformers - Part 10: Determination of sound levels. |
Kenya Power TITLE: DISTRIBUTION TRANSFORNERS Patt 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 6 of 50
"2. REFERENCES
The following standards contain provisions which, through reference in this text constitute provisions
this Specification. Unless otherwise stated, the latest editions (including amendments) apply. of this Specification. Unless otherwise stated, the latest editions (including amendments) apply. ISO 1461: 1461:, Hot dip galvanized, , Specifications and test methods.
Hot dip galvanized coatings on fabricated iron and steel articles Specifications and test methods."
"IEC 60076-1, 2, 3,
Power transformers - Part 1: General; -Part 2: Temperature rise; 4, 5, 7&10: Part 3: Insulation levels dielectric tests and external air clearances; - Part 4: Guide to the lightning impulse testing- power transformers and reactors; - Part 5: Ability to withstand short circuit;- Part 7: Loading guide for oil immersed power transformers - Part 10: Determination of sound levels."
IEC 60554-3-1. Specification for cellulosic paper for electrical purposes- Part 3: Specification for individual materials, sheet 1-General purpose electrical paper.
IEC 60317-0-1: Specifications for particular types of winding wires - Part 0: General requirements -Section 1: Enameled round copper wire
IEC 60296: Specification for unused mineral insulating oil for transformers and switchgear.
IEC 60214: Tap-changers - Part 1: Performance requirements and test methods, Part 2: Application guide
IEC 60512: Connectors for electronic equipment
IEC 60641-3-1: Pressboard and press paper for electrical purposes -Part 3: Specifications for individual materials - Sheet 1: Requirements for pressboard, types B.0.1, B.0.3, B.2.1, B.2.3, B.3.1, B.3.3, B.4.1, B.4.3, B.5.1, B.5.3 and B.6.1
"IEC 60422 .
BS 381C:" Mineral insulating oils in electrical equipment - Supervision and maintenance guidance
Specification for colours for identification coding and special purposes
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date; 2023-01-24 Date: 2023-01-24 | Kenya Power | TITLE: DISTRIBUTION TRANSFORNERS Patt 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 6 of 50 | |
| 2. REFERENCES <br> The following standards contain provisions which, through reference in this text constitute provisions <br> this Specification. Unless otherwise stated, the latest editions (including amendments) apply. of this Specification. Unless otherwise stated, the latest editions (including amendments) apply. ISO 1461: $\begin{array}{ll}\text { 1461: } & \text { Hot dip galvanized } \\ & \text { Specifications and test methods. }\end{array}$ <br> Hot dip galvanized coatings on fabricated iron and steel articles Specifications and test methods. | | | |
| IEC 60076-1, 2, 3, <br> Power transformers - Part 1: General; -Part 2: Temperature rise; 4, 5, 7&10: Part 3: Insulation levels dielectric tests and external air clearances; - Part 4: Guide to the lightning impulse testing- power transformers and reactors; - Part 5: Ability to withstand short circuit;- Part 7: Loading guide for oil immersed power transformers - Part 10: Determination of sound levels. | | | |
| IEC 60554-3-1. | Specification for cellulosic paper for electrical purposes- Part 3: Specification for individual materials, sheet 1-General purpose electrical paper. | | |
| IEC 60317-0-1: | Specifications for particular types of winding wires - Part 0: General requirements -Section 1: Enameled round copper wire | | |
| IEC 60296: | Specification for unused mineral insulating oil for transformers and switchgear. | | |
| IEC 60214: | Tap-changers - Part 1: Performance requirements and test methods, Part 2: Application guide | | |
| IEC 60512: | Connectors for electronic equipment | | |
| IEC 60641-3-1: | Pressboard and press paper for electrical purposes -Part 3: Specifications for individual materials - Sheet 1: Requirements for pressboard, types B.0.1, B.0.3, B.2.1, B.2.3, B.3.1, B.3.3, B.4.1, B.4.3, B.5.1, B.5.3 and B.6.1 | | |
| IEC 60422 . <br> BS 381C: | Mineral insulating oils in electrical equipment - Supervision and maintenance guidance | | |
| | Specification for colours for identification coding and special purposes | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | |
| Signed: | | Signed: | |
| Date; 2023-01-24 | | Date: 2023-01-24 | |
标题: 配电变压器 第 2 部分:柱装三相整体式配电变压器 - 规格
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 7 页,共 50 页
BS EN 50464-1: BS 2627: BS EN 755-6:铝及铝合金。挤压棒材/条材、管材和型材。六角棒材,尺寸和形状公差
BS EN 50464-1:
BS 2627:
BS EN 755-6: Aluminum and aluminum alloys. Extruded rod/bar, tube and profiles. Hexagonal bars, tolerances on dimensions and form| BS EN 50464-1: |
| :--- |
| BS 2627: |
| BS EN 755-6: Aluminum and aluminum alloys. Extruded rod/bar, tube and profiles. Hexagonal bars, tolerances on dimensions and form |
能源部 CFR10 第 431 部分:商业设备节能计划:配电变压器节能标准;最终规则。
《变压器手册》--2006 年 CBIP 第 295 号出版物。
3.术语和定义
参考标准中的术语和定义适用。
4.要求
4.1.服务条件
4.1.1.运行条件
变压器应适合在热带地区室外连续运行,并满足以下条件
a) 高度:最高2,200m2、200 \mathrm{~m} 高于海平面;
b) 温度:+30^(@)C+30^{\circ} 最少-1^(@)C-1^{\circ} 和 max+40^(@)C\max+40^{\circ}\mathrm{C};
c) 湿度:最高95%95 %;d) 污染:根据 IEC 60815 标准,设计污染等级为 "极重"(污染等级 IV); e) 等暴雨等级:每年 180 个雷暴日。
The transformer shall be suitable for continuous outdoor operation in tropical areas with the following conditions.
a) Altitude: up to 2,200m above sea level;
b) Temperature: average of +30^(@)C with a minimum of -1^(@)C and max+40^(@)C;
c) Humidity: up to 95%;
d) Pollution: Design pollution level to be taken as "Very Heavy" (Pollution level IV) in accordance with IEC 60815;
e) Isokeraunic level: 180 thunderstorm days per year.| The transformer shall be suitable for continuous outdoor operation in tropical areas with the following conditions. |
| :--- |
| a) Altitude: up to $2,200 \mathrm{~m}$ above sea level; |
| b) Temperature: average of $+30^{\circ} \mathrm{C}$ with a minimum of $-1^{\circ} \mathrm{C}$ and $\max +40^{\circ} \mathrm{C}$; |
| c) Humidity: up to $95 \%$; |
| d) Pollution: Design pollution level to be taken as "Very Heavy" (Pollution level IV) in accordance with IEC 60815; |
| e) Isokeraunic level: 180 thunderstorm days per year. |
发布者标准制定科科长
授权人:标准部主任
已签署:
签名 t
日期:2023-012024
日期: 2023-01-24
https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-07.jpg?height=182&width=214&top_left_y=172&top_left_x=291 TITLE: DISTRIBUTION TRANSFORNIERS Part 2: Pole Mounted Three Phase Onl Type Distribution Transformer - Specification Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 7 of 50
"BS EN 50464-1:
BS 2627:
BS EN 755-6: Aluminum and aluminum alloys. Extruded rod/bar, tube and profiles. Hexagonal bars, tolerances on dimensions and form"
Department of Energy10 CFR Part 431: Energy Conservation Program for Commercial Equipment: Distribution Transformers Energy Conservation Standards; Final Rule.
Manual on Transformers - Publication No. 295 CBIP 2006.
3. TERMS AND DEFINITIONS
The terms and definitions given in the reference standards shall apply.
4. REQUIREMENTS
4.1. Service Conditions
4.1.1. Operating Conditions
"The transformer shall be suitable for continuous outdoor operation in tropical areas with the following conditions.
a) Altitude: up to 2,200m above sea level;
b) Temperature: average of +30^(@)C with a minimum of -1^(@)C and max+40^(@)C;
c) Humidity: up to 95%;
d) Pollution: Design pollution level to be taken as "Very Heavy" (Pollution level IV) in accordance with IEC 60815;
e) Isokeraunic level: 180 thunderstorm days per year."
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signedt
Date: 2023-012024 Date: 2023-01-24 |  | TITLE: DISTRIBUTION TRANSFORNIERS Part 2: Pole Mounted Three Phase Onl Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 7 of 50 | |
| BS EN 50464-1: <br> BS 2627: <br> BS EN 755-6: Aluminum and aluminum alloys. Extruded rod/bar, tube and profiles. Hexagonal bars, tolerances on dimensions and form | | | |
| | | | | |
| Department of Energy10 CFR Part 431: Energy Conservation Program for Commercial Equipment: Distribution Transformers Energy Conservation Standards; Final Rule. | | | |
| Manual on Transformers - Publication No. 295 CBIP 2006. | | | |
| 3. TERMS AND DEFINITIONS | | | |
| The terms and definitions given in the reference standards shall apply. | | | |
| 4. REQUIREMENTS | | | |
| 4.1. Service Conditions | | | |
| 4.1.1. Operating Conditions | | | |
| The transformer shall be suitable for continuous outdoor operation in tropical areas with the following conditions. <br> a) Altitude: up to $2,200 \mathrm{~m}$ above sea level; <br> b) Temperature: average of $+30^{\circ} \mathrm{C}$ with a minimum of $-1^{\circ} \mathrm{C}$ and $\max +40^{\circ} \mathrm{C}$; <br> c) Humidity: up to $95 \%$; <br> d) Pollution: Design pollution level to be taken as "Very Heavy" (Pollution level IV) in accordance with IEC 60815; <br> e) Isokeraunic level: 180 thunderstorm days per year. | | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | |
| Signed: | | Signedt | |
| Date: 2023-012024 | | Date: 2023-01-24 | |
Kenya Power TITLE: DISTRIBUTION TRANSFORMERS Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 8 of 50
4.1.2. System characteristics
4.1.2.1. The transformer will be connected to overhead system which is of unearthed construction (i.e. without continuous aerial earth wire).
4.1.2.2 The primary system is having a nominal voltage of 11,000 volts and 33,000 volts and system highest voltage of 12,000 volts and 36,000 volts respectively. The primary system is three-phase 3 -wire, 50 Hz and the secondary is 420 volts three-phase 4 -wire.
4.1.2.3. The Transformer shall be operated at a high loading factor as per IEC 60076-7.
4.2. General Requirements
4.2.1 The transformer shall be outdoor, oil-immersed, of ONAN classification and core type windings designed, manufactured and tested in accordance with IEC 60076-1 and all relevant parts (latest editions). Any deviations/additional requirements shall be as stated in this specification.
4.2.2. The transformer shall be designed for a service life of at least twenty-five (25) years as per IEC 60076-7 Table 3.
4.2.3. The transformer shall be a two winding type three-phase integral unit with connections and phase displacements symbols clearly marked on the nameplate i.e. D for high voltage and y & n for low voltage.
Note: The expansion of the oil shall be taken by elastic movement of the permanently sealed corrugated tanks or radiators.
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
"Signed:
Date: 2023-61-24" Signed:
Date: 2023-01-24 | Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- | :--- |
| | | | Issue No. | 7 |
| | | | Revision No. | 0 |
| | | | Date of Issue | 2023-01-24 |
| | | | Page 8 of 50 | |
| 4.1.2. System characteristics | | | | |
| 4.1.2.1. The transformer will be connected to overhead system which is of unearthed construction (i.e. without continuous aerial earth wire). | | | | |
| 4.1.2.2 The primary system is having a nominal voltage of 11,000 volts and 33,000 volts and system highest voltage of 12,000 volts and 36,000 volts respectively. The primary system is three-phase 3 -wire, 50 Hz and the secondary is 420 volts three-phase 4 -wire. | | | | |
| 4.1.2.3. The Transformer shall be operated at a high loading factor as per IEC 60076-7. | | | | |
| 4.2. General Requirements | | | | |
| 4.2.1 The transformer shall be outdoor, oil-immersed, of ONAN classification and core type windings designed, manufactured and tested in accordance with IEC 60076-1 and all relevant parts (latest editions). Any deviations/additional requirements shall be as stated in this specification. | | | | |
| 4.2.2. The transformer shall be designed for a service life of at least twenty-five (25) years as per IEC 60076-7 Table 3. | | | | |
| 4.2.3. The transformer shall be a two winding type three-phase integral unit with connections and phase displacements symbols clearly marked on the nameplate i.e. $\mathbf{D}$ for high voltage and $\mathbf{y}$ & $\mathbf{n}$ for low voltage. | | | | |
| Note: The expansion of the oil shall be taken by elastic movement of the permanently sealed corrugated tanks or radiators. | | | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | | |
| Signed: <br> Date: 2023-61-24 | | Signed: | | |
| | | Date: 2023-01-24 | | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distributiom Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distributiom Transformer - Specification |
4.2.5. The transformer and its component parts shall be able to carry loading beyond rated power under permissible loading given in IEC 60076-7, Table 4 and clause 4.3 .2 for distribution transformers. The bushings, tap changers and other auxiliary equipment shall be selected so as not to restrict the loading capability of the transformer shall be designed to facilitate operation, inspection, maintenance and repairs.
4.2.6. The transformer shall be designed to minimize the risk of accidental short-circuit caused by animals, birds or vermin. The manufacturer shall consider the safely of operators and maintenance staff in the design of the transformer in particular the following aspects as per clause 9.1.2 of IEC 60076-1:2011.
(i) Accessibility to parts with high temperatures
(ii) Accessibility to live parts
(iii)Lifting and handling provisions
(iv) Access for maintenance
(v) Working at a height| 4.2.5. The transformer and its component parts shall be able to carry loading beyond rated power under permissible loading given in IEC 60076-7, Table 4 and clause 4.3 .2 for distribution transformers. The bushings, tap changers and other auxiliary equipment shall be selected so as not to restrict the loading capability of the transformer shall be designed to facilitate operation, inspection, maintenance and repairs. |
| :--- |
| 4.2.6. The transformer shall be designed to minimize the risk of accidental short-circuit caused by animals, birds or vermin. The manufacturer shall consider the safely of operators and maintenance staff in the design of the transformer in particular the following aspects as per clause 9.1.2 of IEC 60076-1:2011. |
| (i) Accessibility to parts with high temperatures |
| (ii) Accessibility to live parts |
| (iii)Lifting and handling provisions |
| (iv) Access for maintenance |
| (v) Working at a height |
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distributiom Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 9 of 50
"4.2.5. The transformer and its component parts shall be able to carry loading beyond rated power under permissible loading given in IEC 60076-7, Table 4 and clause 4.3 .2 for distribution transformers. The bushings, tap changers and other auxiliary equipment shall be selected so as not to restrict the loading capability of the transformer shall be designed to facilitate operation, inspection, maintenance and repairs.
4.2.6. The transformer shall be designed to minimize the risk of accidental short-circuit caused by animals, birds or vermin. The manufacturer shall consider the safely of operators and maintenance staff in the design of the transformer in particular the following aspects as per clause 9.1.2 of IEC 60076-1:2011.
(i) Accessibility to parts with high temperatures
(ii) Accessibility to live parts
(iii)Lifting and handling provisions
(iv) Access for maintenance
(v) Working at a height"
4.2.7. All parts of the transformer, including bushing insulators with their mountings, shall be designed to eliminate pockets of water. The top cover shall be inclined so that rain water shall not collect anywhere on the top cover; the gaskets shall be concealed by an overlap between the top cover and tank flanges by 10 mm width. To avoid seepage of water into the tank, all bushings and any other fitting on top cover shall either be inclined or bevelled such that they are raised by a minimum 3 mm from the surface of the top cover.
4.2.8. Corresponding parts including bushings liable to be replaced shall be interchangeable.
4.2.9. The design of fittings and accessories shall not allow for siphoning of oil by vandals. All fittings and accessories shall be secured from the inside of the transformer and/or have small openings that do not allow for oil siphoning.
4.2.10. All components and materials used in the construction of the transformer shall comply with the requirements of the relevant IEC/ISO standards where they exist unless otherwise stated. Type Test Reports from ISO/IEC 17025 accredited laboratories for these component parts and materials from respective manufacturers shall be submitted for tender evaluation to verify conformity to their respective manufacturing standards.
Issued by: Head of Section, Standard development
"Signed:
Date: 2023-01-24" Date: 2023-01-24 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distributiom Transformer - Specification | | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- | :--- |
| | | | Issue No. | 7 |
| | | | Revision No. | 0 |
| | | | Date of Issue | 2023-01-24 |
| | | | Page 9 of 50 | |
| 4.2.5. The transformer and its component parts shall be able to carry loading beyond rated power under permissible loading given in IEC 60076-7, Table 4 and clause 4.3 .2 for distribution transformers. The bushings, tap changers and other auxiliary equipment shall be selected so as not to restrict the loading capability of the transformer shall be designed to facilitate operation, inspection, maintenance and repairs. <br> 4.2.6. The transformer shall be designed to minimize the risk of accidental short-circuit caused by animals, birds or vermin. The manufacturer shall consider the safely of operators and maintenance staff in the design of the transformer in particular the following aspects as per clause 9.1.2 of IEC 60076-1:2011. <br> (i) Accessibility to parts with high temperatures <br> (ii) Accessibility to live parts <br> (iii)Lifting and handling provisions <br> (iv) Access for maintenance <br> (v) Working at a height | | | | |
| | | | | | | |
| | | | | | | |
| 4.2.7. All parts of the transformer, including bushing insulators with their mountings, shall be designed to eliminate pockets of water. The top cover shall be inclined so that rain water shall not collect anywhere on the top cover; the gaskets shall be concealed by an overlap between the top cover and tank flanges by 10 mm width. To avoid seepage of water into the tank, all bushings and any other fitting on top cover shall either be inclined or bevelled such that they are raised by a minimum 3 mm from the surface of the top cover. | | | | |
| 4.2.8. Corresponding parts including bushings liable to be replaced shall be interchangeable. | | | | |
| 4.2.9. The design of fittings and accessories shall not allow for siphoning of oil by vandals. All fittings and accessories shall be secured from the inside of the transformer and/or have small openings that do not allow for oil siphoning. | | | | |
| 4.2.10. All components and materials used in the construction of the transformer shall comply with the requirements of the relevant IEC/ISO standards where they exist unless otherwise stated. Type Test Reports from ISO/IEC 17025 accredited laboratories for these component parts and materials from respective manufacturers shall be submitted for tender evaluation to verify conformity to their respective manufacturing standards. | | | | |
| Issued by: Head of Section, Standard development | | | | |
| Signed: <br> Date: 2023-01-24 | | Date: 2023-01-24 | | |
肯尼亚电力公司
标题: 配电变压器 第 2 点: 杆装三相油式配电变压器 - 规格
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 10 页,共 50 页
4.2.11.所有载流表面--连接和触点必须有足够的横截面积,适合持续载流能力而不会过度发热。固定连接必须用符合 ISO 898-1 和 2 标准的适当尺寸的螺栓和螺母或固定螺钉固定,并牢牢拧紧。带电流的螺柱连接应使用锁紧螺母。从绕组到套管端子的所有导线都必须有足够的支撑,以防止振动造成损坏,包括短路情况下的系统拉力。载流部件上的所有螺栓和螺母均应由黄铜制成,至少应含 70%70 \% 铜。
4.2.12.变压器制造过程中使用的材料和工艺应与绝缘油相容,并避免绝缘油中产生酸性。
4.2.13.最大噪音水平应符合 BS EN 50464-1 和表 5 的规定。声级应按照 IEC 60076-1060076-10 或 NEMA TR1 测量和测试,且不得超过保证的最大声级(无公差)。保证值应在评标书中说明。
4.2.17. Design drawings (by the manufacturer) complete with manufacturer's guaranteed technical particulars (GTP) shall be submitted to KPLC for approval before manufacture. The design drawings shall be detailed and shall include a minimum of the following:
a) Overall dimensions of the transformer and relevant electrical clearances. This shall include all perspectives and respective| 4.2.17. Design drawings (by the manufacturer) complete with manufacturer's guaranteed technical particulars (GTP) shall be submitted to KPLC for approval before manufacture. The design drawings shall be detailed and shall include a minimum of the following: |
| :--- |
| a) Overall dimensions of the transformer and relevant electrical clearances. This shall include all perspectives and respective |
Kenya Power TITLE: DISTRIBUTION TRANSFORMERS Patt 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 10 of 50
4.2.11. All current carrying surfaces - connections and contacts shall provide adequate cross-sectional area suitable for continuous current carrying capacity without undue heating. Fixed connections shall be secured by bolts & nuts or set screws to ISO 898-1 & 2 of adequate sizes, securely tightened. Lock nuts shall be used on stud connections carrying current. All leads from the winding to the terminals of the bushings shall be adequately supported to prevent damages caused by vibrations including a systematical pull under short circuit conditions. All bolts and nuts in current carrying parts shall be made of brass with at least 70% copper content.
4.2.12. The choice of materials and processes used in the manufacture of the transformer, shall be compatible with the insulating oil and avoid development of acidity in the insulating oil.
4.2.13. The maximum noise levels shall be in accordance with BS EN 50464-1 and Table 5. The sound level shall be measured and tested in accordance with IEC 60076-10 or NEMA TR1 and shall not exceed the guaranteed maximum level (without tolerance). The guaranteed values shall be stated in the bid for tender evaluation.
4.2.14. The transformer shall be designed to withstand a constant accelcration of at least lgin all directions (in addition to the acceleration due to gravity in the vertical directions) without any damage, demonstrated by static force calculations based on a constant value of acceleration as per clause 5.7.4 . 2 of IEC 60076-1;2011.
4.2.15. Each transformer shall be suitable for pole mounting on steel channels. It shall be complete with two steel channels under base with suitable mounting holes two holes.
4.2.16. Drawings and documentation for each size of transformer offered shall be submitted with tender, clearly detailing important dimensions, any special features of the offered design, clearances, accessories, fittings and the features of the offered design that make it impossible for vandals to siphon oil from the transformer even after forceful breakage of accessory/fitting.
"4.2.17. Design drawings (by the manufacturer) complete with manufacturer's guaranteed technical particulars (GTP) shall be submitted to KPLC for approval before manufacture. The design drawings shall be detailed and shall include a minimum of the following:
a) Overall dimensions of the transformer and relevant electrical clearances. This shall include all perspectives and respective"
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
"Signed:
Date: 2023-0124" Signed:
Date: 2023-01-24 | Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS Patt 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- | :--- |
| | | | Issue No. | 7 |
| | | | Revision No. | 0 |
| | | | Date of Issue | 2023-01-24 |
| | | | Page 10 of 50 | |
| 4.2.11. All current carrying surfaces - connections and contacts shall provide adequate cross-sectional area suitable for continuous current carrying capacity without undue heating. Fixed connections shall be secured by bolts & nuts or set screws to ISO 898-1 & 2 of adequate sizes, securely tightened. Lock nuts shall be used on stud connections carrying current. All leads from the winding to the terminals of the bushings shall be adequately supported to prevent damages caused by vibrations including a systematical pull under short circuit conditions. All bolts and nuts in current carrying parts shall be made of brass with at least $70 \%$ copper content. | | | | |
| 4.2.12. The choice of materials and processes used in the manufacture of the transformer, shall be compatible with the insulating oil and avoid development of acidity in the insulating oil. | | | | |
| 4.2.13. The maximum noise levels shall be in accordance with BS EN 50464-1 and Table 5. The sound level shall be measured and tested in accordance with IEC $60076-10$ or NEMA TR1 and shall not exceed the guaranteed maximum level (without tolerance). The guaranteed values shall be stated in the bid for tender evaluation. | | | | |
| 4.2.14. The transformer shall be designed to withstand a constant accelcration of at least lgin all directions (in addition to the acceleration due to gravity in the vertical directions) without any damage, demonstrated by static force calculations based on a constant value of acceleration as per clause 5.7.4 . 2 of IEC 60076-1;2011. | | | | |
| 4.2.15. Each transformer shall be suitable for pole mounting on steel channels. It shall be complete with two steel channels under base with suitable mounting holes two holes. | | | | |
| 4.2.16. Drawings and documentation for each size of transformer offered shall be submitted with tender, clearly detailing important dimensions, any special features of the offered design, clearances, accessories, fittings and the features of the offered design that make it impossible for vandals to siphon oil from the transformer even after forceful breakage of accessory/fitting. | | | | |
| 4.2.17. Design drawings (by the manufacturer) complete with manufacturer's guaranteed technical particulars (GTP) shall be submitted to KPLC for approval before manufacture. The design drawings shall be detailed and shall include a minimum of the following: <br> a) Overall dimensions of the transformer and relevant electrical clearances. This shall include all perspectives and respective | | | | |
| Issued by: Head of Section, Standard development | | | Authorized by: Head of Department, Standards | |
| Signed: <br> Date: 2023-0124 | | | Signed: | |
| | | | Date: 2023-01-24 | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装式三相 Oul 型配电变压器 - 规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oul Type Distribution Transforner - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oul Type Distribution Transforner - Specification |
(i) Weights of oil,
(ii) Weight of LV winding conductor
(iii) Weight of HV winding conductor
(iv) Core material
(v) Copper winding material
(vi) Insulating materials and
(vii) Steel tank/core clamp structure
b) Core/coil/ insulation dimensions, clearances (internal and external) and stacking/coil winding sequence detail
c) Drawing of nameplate to scale
d) Dimensional drawing of bushings, tap-changer and clamps.
e) Legend for all technical engineering drawings with manufacturer name, logo, model number, revision/drawing number and key
f) Detailed drawing of surge arrestor, its mounting and constituent parts.
g) Detailed drawing of arcing horns where applicable.| (i) Weights of oil, |
| :--- |
| (ii) Weight of LV winding conductor |
| (iii) Weight of HV winding conductor |
| (iv) Core material |
| (v) Copper winding material |
| (vi) Insulating materials and |
| (vii) Steel tank/core clamp structure |
| b) Core/coil/ insulation dimensions, clearances (internal and external) and stacking/coil winding sequence detail |
| c) Drawing of nameplate to scale |
| d) Dimensional drawing of bushings, tap-changer and clamps. |
| e) Legend for all technical engineering drawings with manufacturer name, logo, model number, revision/drawing number and key |
| f) Detailed drawing of surge arrestor, its mounting and constituent parts. |
| g) Detailed drawing of arcing horns where applicable. |
4.3.2. The transformer shall be capable of carrying its full normal rating continuously at any tap under the conditions stated in clause 4.1 without;
(i) Undue stress,
(ii) Overheating, or
(iii) Temperature rise in exceeding 50^(@)C in top oil or 55^(@)C in windings above ambient.
(iv) Temperature rise of winding hotspot and of metallic part in contact with cellulose outside the winding block shall not exceed 65^(@)C, above ambient, as per IEC 60076-7 Table 4.| 4.3.2. The transformer shall be capable of carrying its full normal rating continuously at any tap under the conditions stated in clause 4.1 without; |
| :--- |
| (i) Undue stress, |
| (ii) Overheating, or |
| (iii) Temperature rise in exceeding $50^{\circ} \mathrm{C}$ in top oil or $55^{\circ} \mathrm{C}$ in windings above ambient. |
| (iv) Temperature rise of winding hotspot and of metallic part in contact with cellulose outside the winding block shall not exceed $65^{\circ} \mathrm{C}$, above ambient, as per IEC 60076-7 Table 4. |
Kenya Power "TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oul Type Distribution Transforner - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 11 of 50
"(i) Weights of oil,
(ii) Weight of LV winding conductor
(iii) Weight of HV winding conductor
(iv) Core material
(v) Copper winding material
(vi) Insulating materials and
(vii) Steel tank/core clamp structure
b) Core/coil/ insulation dimensions, clearances (internal and external) and stacking/coil winding sequence detail
c) Drawing of nameplate to scale
d) Dimensional drawing of bushings, tap-changer and clamps.
e) Legend for all technical engineering drawings with manufacturer name, logo, model number, revision/drawing number and key
f) Detailed drawing of surge arrestor, its mounting and constituent parts.
g) Detailed drawing of arcing horns where applicable."
NOTE: All design drawings MUST BE stamped and signed by the manufacturer's authorized personnel.
4.3. Ratings
4.3.1. The transformers covered by this Specification shall be of the following ratings:
"(a) 11000//420V:50KVA,100KVA,200KVA and 315 KVA
(b) 33000//420V:50KVA,100KVA,200KVA and 315 KVA ."
"4.3.2. The transformer shall be capable of carrying its full normal rating continuously at any tap under the conditions stated in clause 4.1 without;
(i) Undue stress,
(ii) Overheating, or
(iii) Temperature rise in exceeding 50^(@)C in top oil or 55^(@)C in windings above ambient.
(iv) Temperature rise of winding hotspot and of metallic part in contact with cellulose outside the winding block shall not exceed 65^(@)C, above ambient, as per IEC 60076-7 Table 4."
NOTE: The loading capabilities shall be demonstrated by a temperature rise test. This test shall be done in the presence of Kenya Power representatives during factory acceptance testing.
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
"Signed:
Date: 2023-124" Signed:
Date: 2023-01-24 | Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oul Type Distribution Transforner - Specification | | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- | :--- |
| | | | Issue No . | 7 |
| | | | Revision No. | 0 |
| | | | Date of Issue | 2023-01-24 |
| | | | Page 11 of 50 | |
| (i) Weights of oil, <br> (ii) Weight of LV winding conductor <br> (iii) Weight of HV winding conductor <br> (iv) Core material <br> (v) Copper winding material <br> (vi) Insulating materials and <br> (vii) Steel tank/core clamp structure <br> b) Core/coil/ insulation dimensions, clearances (internal and external) and stacking/coil winding sequence detail <br> c) Drawing of nameplate to scale <br> d) Dimensional drawing of bushings, tap-changer and clamps. <br> e) Legend for all technical engineering drawings with manufacturer name, logo, model number, revision/drawing number and key <br> f) Detailed drawing of surge arrestor, its mounting and constituent parts. <br> g) Detailed drawing of arcing horns where applicable. | | | | |
| NOTE: All design drawings MUST BE stamped and signed by the manufacturer's authorized personnel. | | | | |
| 4.3. Ratings | | | | |
| 4.3.1. The transformers covered by this Specification shall be of the following ratings: | | | | |
| (a) $11000 / 420 \mathrm{~V}: 50 \mathrm{KVA}, 100 \mathrm{KVA}, 200 \mathrm{KVA}$ and 315 KVA <br> (b) $33000 / 420 \mathrm{~V}: 50 \mathrm{KVA}, 100 \mathrm{KVA}, 200 \mathrm{KVA}$ and 315 KVA . | | | | |
| 4.3.2. The transformer shall be capable of carrying its full normal rating continuously at any tap under the conditions stated in clause 4.1 without; <br> (i) Undue stress, <br> (ii) Overheating, or <br> (iii) Temperature rise in exceeding $50^{\circ} \mathrm{C}$ in top oil or $55^{\circ} \mathrm{C}$ in windings above ambient. <br> (iv) Temperature rise of winding hotspot and of metallic part in contact with cellulose outside the winding block shall not exceed $65^{\circ} \mathrm{C}$, above ambient, as per IEC 60076-7 Table 4. | | | | |
| NOTE: The loading capabilities shall be demonstrated by a temperature rise test. This test shall be done in the presence of Kenya Power representatives during factory acceptance testing. | | | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | | |
| Signed: <br> Date: 2023-124 | | Signed: | | |
| | | Date: 2023-01-24 | | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
Kenya Power "TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 12 of 50
4.3.3. The transformer shall be capable of withstanding the maximum fault level at its rated voltage and impedance for three (3) seconds. The design shall cater for the expected lifetime of the transformer. As a minimum, the short-circuit apparent power of 11 kV and 33 kV systems shall be taken as 600MVA and 1500MVA respectively (as per IEC 60076-5) in order to obtain the value of the symmetrical short circuit current to be used for the design and tests.
4.3.4 The thermal ability of the offered transformer design to withstand short circuit shall be demonstrated by calculation carried out in accordance with the requirements of clause 4.1.1 to 4.1.5 of IEC 60076-5.
4.3.5. The calculation showing details and compliance with the requirements of clause 4.1 .1 to 4.1.5 of IEC 60076-5 shall be submitted with tender for purposes of tender evaluation. The duration of the current to be used for the calculation of the thermal ability to withstand short circuit shall be three (3) seconds as per IEC 60076-5.
4.3.6. The ability of the transformer to withstand the dynamic effects of short circuit shall be demonstrated by tests and complete test reports (including oscillograms and records of the condition of the transformer before and after the short-circuit test) shall be submitted with the bid for tender evaluation.
4.4. Winding, Insulation and Connections
4.4.1. General
4.4.1.1. The transformer vector group shall be Dyn11 with respect to the 11 kV windings (or 33 kV as appropriate) and low voltage winding (420V) as per Annex D of IEC 60076-1:2011. The star point of the low voltage winding shall be brought out to a neutral bushing of the same size as the LV phase bushing and rod.
4.4.1.2. The transformer shall be capable of operation without danger on any particular tapping at the rated KVA when the voltage may vary by +20% and -5% of the voltage corresponding to the tapping.
4.4.1.3. The windings and connections as well as the insulating material shall not soften, ooze, shrink or collapse during service. The materials shall be non-catalytic and chemically inactive in transformer oil during service.
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
"Signed:
Date: 2023-01-24" Date: 2023-01-24
| Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 12 of 50 | |
| 4.3.3. The transformer shall be capable of withstanding the maximum fault level at its rated voltage and impedance for three (3) seconds. The design shall cater for the expected lifetime of the transformer. As a minimum, the short-circuit apparent power of 11 kV and 33 kV systems shall be taken as 600MVA and 1500MVA respectively (as per IEC 60076-5) in order to obtain the value of the symmetrical short circuit current to be used for the design and tests. | | | |
| 4.3.4 The thermal ability of the offered transformer design to withstand short circuit shall be demonstrated by calculation carried out in accordance with the requirements of clause 4.1.1 to 4.1.5 of IEC 60076-5. | | | |
| 4.3.5. The calculation showing details and compliance with the requirements of clause 4.1 .1 to 4.1.5 of IEC $60076-5$ shall be submitted with tender for purposes of tender evaluation. The duration of the current to be used for the calculation of the thermal ability to withstand short circuit shall be three (3) seconds as per IEC 60076-5. | | | |
| 4.3.6. The ability of the transformer to withstand the dynamic effects of short circuit shall be demonstrated by tests and complete test reports (including oscillograms and records of the condition of the transformer before and after the short-circuit test) shall be submitted with the bid for tender evaluation. | | | |
| 4.4. Winding, Insulation and Connections | | | |
| 4.4.1. General | | | |
| 4.4.1.1. The transformer vector group shall be Dyn11 with respect to the 11 kV windings (or 33 kV as appropriate) and low voltage winding (420V) as per Annex D of IEC 60076-1:2011. The star point of the low voltage winding shall be brought out to a neutral bushing of the same size as the LV phase bushing and rod. | | | |
| 4.4.1.2. The transformer shall be capable of operation without danger on any particular tapping at the rated KVA when the voltage may vary by $+20 \%$ and $-5 \%$ of the voltage corresponding to the tapping. | | | |
| 4.4.1.3. The windings and connections as well as the insulating material shall not soften, ooze, shrink or collapse during service. The materials shall be non-catalytic and chemically inactive in transformer oil during service. | | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | |
| Signed: <br> Date: 2023-01-24 | | Date: 2023-01-24 | |
| | | | |
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
4.4.2.1. The secondary windings shall be either:
(i) Enameled round copper wire or foil /strip of copper as per IEC 60317-1 OR;
(ii) Strip of aluminum-The aluminum shall be of either grade 1050,1060,1070 or 1350 with at least 99.50% aluminum equivalent to 61% conductivity of copper with properties conforming to BS 2898 and Table 2. The winding shall be full coiling without segmenting.| 4.4.2.1. The secondary windings shall be either: |
| :--- |
| (i) Enameled round copper wire or foil /strip of copper as per IEC 60317-1 OR; |
| (ii) Strip of aluminum-The aluminum shall be of either grade $1050,1060,1070$ or 1350 with at least $99.50 \%$ aluminum equivalent to $61 \%$ conductivity of copper with properties conforming to BS 2898 and Table 2. The winding shall be full coiling without segmenting. |
The characteristics of copper and aluminum required shall be as per IEC 60076-5 and Table 1:
Table 1: Characteristics of copper and aluminum winding wire| The characteristics of copper and aluminum required shall be as per IEC 60076-5 and Table 1: |
| :--- |
| Table 1: Characteristics of copper and aluminum winding wire |
"TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 13 of 50
4.4.2. Winding material
The primary windings shall be made of Grade 3, super enameled round copper wire as per IEC 60317-0-1 or shaped aluminum coil conforming to BS 2627 or superior quality. The winding shall be full coiling. The characteristics of copper and aluminum required shall be as per IEC 60076-5 and Table 1.
"4.4.2.1. The secondary windings shall be either:
(i) Enameled round copper wire or foil /strip of copper as per IEC 60317-1 OR;
(ii) Strip of aluminum-The aluminum shall be of either grade 1050,1060,1070 or 1350 with at least 99.50% aluminum equivalent to 61% conductivity of copper with properties conforming to BS 2898 and Table 2. The winding shall be full coiling without segmenting."
4.4.2.2. The current density in LV winding shall not exceed 2.8A//mm^(2) for copper and 1.4A//mm^(2) for aluminum winding. The current density in HV winding shall not exceed 2.8A//mm^(2) for copper and 1.4A//mm^(2) for aluminum winding. This will be confirmed through the relationship: Conductor area = Current per phase/Current density.
"The characteristics of copper and aluminum required shall be as per IEC 60076-5 and Table 1:
Table 1: Characteristics of copper and aluminum winding wire"
"Property
Material
Copper
Aluminum
Specific heat at 100^(@)C(J//kg*^(@)C)
398.4
928
Density at 100^(@)C(kg//m^(3))
8,894
2,685
Resistivity at 100^(@)C(mu Omega-m)
0.0224
0.0355"
Table 2: Characteristics of copper and aluminum foil/strip
Property Material
Copper Aluminum
Ultimate Tensile Strength, N//mm^(2) 205-250 60-95
>30 > 25
Density at 20^(@)C(kg//dm^(3)) 8.91 2.703
Maximum resistance at 20^(@)C(mu Omega//m) <= 0.01734 <= 0.02825 | | | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- | :--- | :--- |
| | | Issue No . | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 13 of 50 |
| 4.4.2. Winding material | | | | | |
| The primary windings shall be made of Grade 3, super enameled round copper wire as per IEC $60317-0-1$ or shaped aluminum coil conforming to BS 2627 or superior quality. The winding shall be full coiling. The characteristics of copper and aluminum required shall be as per IEC 60076-5 and Table 1. | | | | | |
| 4.4.2.1. The secondary windings shall be either: <br> (i) Enameled round copper wire or foil /strip of copper as per IEC 60317-1 OR; <br> (ii) Strip of aluminum-The aluminum shall be of either grade $1050,1060,1070$ or 1350 with at least $99.50 \%$ aluminum equivalent to $61 \%$ conductivity of copper with properties conforming to BS 2898 and Table 2. The winding shall be full coiling without segmenting. | | | | | |
| 4.4.2.2. The current density in LV winding shall not exceed $2.8 \mathrm{~A} / \mathrm{mm}^{2}$ for copper and $1.4 \mathrm{~A} / \mathrm{mm}^{2}$ for aluminum winding. The current density in HV winding shall not exceed $2.8 \mathrm{~A} / \mathrm{mm}^{2}$ for copper and $1.4 \mathrm{~A} / \mathrm{mm}^{2}$ for aluminum winding. This will be confirmed through the relationship: Conductor area $=$ Current per phase/Current density. | | | | | |
| The characteristics of copper and aluminum required shall be as per IEC 60076-5 and Table 1: <br> Table 1: Characteristics of copper and aluminum winding wire | | | | | |
| | Property <br> Material <br> Copper <br> Aluminum <br> Specific heat at $100^{\circ} \mathrm{C}\left(\mathrm{J} / \mathrm{kg} \cdot{ }^{\circ} \mathrm{C}\right)$ <br> 398.4 <br> 928 <br> Density at $100^{\circ} \mathrm{C}\left(\mathrm{kg} / \mathrm{m}^{3}\right)$ <br> 8,894 <br> 2,685 <br> Resistivity at $100^{\circ} \mathrm{C}(\mu \Omega-\mathrm{m})$ <br> 0.0224 <br> 0.0355 | | | | |
| | | | | | | | |
| | | | | | | | |
| | | | | | | | |
| | | | | | | | |
| | Table 2: Characteristics of copper and aluminum foil/strip | | | | | |
| | Property | | Material | | |
| | | | Copper | Aluminum | |
| | | Ultimate Tensile Strength, $\mathrm{N} / \mathrm{mm}^{2}$ | 205-250 | 60-95 | |
| | | | >30 | $>25$ | |
| | | Density at $20^{\circ} \mathrm{C}\left(\mathrm{kg} / \mathrm{dm}^{3}\right)$ | 8.91 | 2.703 | |
| | | Maximum resistance at $20^{\circ} \mathrm{C}(\mu \Omega / \mathrm{m})$ | $\leq 0.01734$ | $\leq 0.02825$ | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 14 页,共 50 页
注:KPLC 将检查和/或测试内置绕组的质量、铜或铝的重量、绝缘材料的特性以及线圈组件的总重量。在阶段检查中还应检查不同绕组所用导体的尺寸,以检查电流密度。 4.4.3.绝缘材料 4.4.3.1.高压绕组和低压绕组应分开,以便于冷却和维修。变压器分接开关的绝缘套管应使用皱纹纸,层间绝缘应使用牛皮纸/纤维素纸、 压纸和/或皱纹纸。
4.4.3.2.铜绕组导体必须有双层搪瓷绝缘。绝缘应为 A 级,温度等级为 符合 IEC 60085 标准。4.4.3.3.绝缘材料的物理和电气特性如下: a) 压纸 压纸应为 K 级热升级压纸或 K 级 T/U 菱形点压纸(thermopox)。 (i) K 级热升华压纸 K 级热升华压纸应由硫酸盐木浆制成,主要用作油浸式配电变压器低压和高压绕组的层间绝缘纸。热升华纸是一种纤维素纸,经过化学改性以降低纸张的分解速度。当暴露在高温下时,热升华纸张应能保持比未经处理的纸张高得多的抗张强度和爆裂强度。表 3 所示的技术特性应符合 IEC 60641-2 和 IEC 60243-1。(ii) K 级--金刚石网点压力纸--带 Bstage 树脂网点的电气绝缘压力纸 K 级 T/U 金刚石网点压力纸(thermopox)是一种压力纸,其质量可提高油浸变压器绕组的机械 强度,同时不会降低局部放电水平,符合 IEC 标准 60641-2 和 60243-1。 b) 皱纹纸
Note: KPLC will inspect and/or test built-up winding for its quality, weight of copper or aluminum, insulation materials properties and overall weight of coil assembly. The size of conductor used for different windings shall also be checked during stage inspection to check the current density.
4.4.3. Insulating materials
4.4.3.1. The HV and LV windings shall be separated so as to allow for cooling and ease of repair. Insulating sleeves for the transformer tapping's shall be in crepe paper and inter layer insulation shall be in Kraft Paper/ cellulosic paper, press paper and/or crepe paper.
4.4.3.2. There shall be double layer enamel insulation for the copper winding conductor. The insulation shall be of class A with temperature class of 105^(@)C as per IEC 60085.
4.4.3.3. Physical and electrical properties of insulation materials shall be as follows:
a) Press paper
Press paper shall be either a Grade K Thermally Upgraded Press paper or Grade K T/U diamond dotted press-paper (thermopox).
(i) Grade K Thermally Upgraded Press paper
Grade K Thermally Upgraded Press paper shall be made of sulphate wood pulp and used mainly as a layer insulating paper in low voltage and high voltage windings of oil immersed distribution transformers. Thermally upgraded paper is a cellulose based paper that has been chemically modified to reduce the rate at which the paper decomposes. Thermally upgraded paper shall be able to retain a much higher tensile and bursting strength than untreated papers when exposed to elevated temperatures. The technical characteristics shown in Table 3 shall be as per IEC 60641-2 and IEC 60243-1.
(ii) Grade K - Diamond dotted press paper - Electrical insulating press papers with Bstage resin dots
Grade K T/U diamond dotted press-paper (thermopox) is a press paper with qualities to improve the mechanical strength of oil immersed transformer windings without reducing partial discharge levels in accordance with IEC Standards 60641-2 and 60243-1.
b) Crepe paper| Note: KPLC will inspect and/or test built-up winding for its quality, weight of copper or aluminum, insulation materials properties and overall weight of coil assembly. The size of conductor used for different windings shall also be checked during stage inspection to check the current density. |
| :--- |
| 4.4.3. Insulating materials |
| 4.4.3.1. The HV and LV windings shall be separated so as to allow for cooling and ease of repair. Insulating sleeves for the transformer tapping's shall be in crepe paper and inter layer insulation shall be in Kraft Paper/ cellulosic paper, press paper and/or crepe paper. |
| 4.4.3.2. There shall be double layer enamel insulation for the copper winding conductor. The insulation shall be of class A with temperature class of $105^{\circ} \mathrm{C}$ as per IEC 60085. |
| 4.4.3.3. Physical and electrical properties of insulation materials shall be as follows: |
| a) Press paper |
| Press paper shall be either a Grade K Thermally Upgraded Press paper or Grade K T/U diamond dotted press-paper (thermopox). |
| (i) Grade K Thermally Upgraded Press paper |
| Grade K Thermally Upgraded Press paper shall be made of sulphate wood pulp and used mainly as a layer insulating paper in low voltage and high voltage windings of oil immersed distribution transformers. Thermally upgraded paper is a cellulose based paper that has been chemically modified to reduce the rate at which the paper decomposes. Thermally upgraded paper shall be able to retain a much higher tensile and bursting strength than untreated papers when exposed to elevated temperatures. The technical characteristics shown in Table 3 shall be as per IEC 60641-2 and IEC 60243-1. |
| (ii) Grade K - Diamond dotted press paper - Electrical insulating press papers with Bstage resin dots |
| Grade K T/U diamond dotted press-paper (thermopox) is a press paper with qualities to improve the mechanical strength of oil immersed transformer windings without reducing partial discharge levels in accordance with IEC Standards 60641-2 and 60243-1. |
| b) Crepe paper |
发布者标准制定科科长
授权人:标准部主任
已签署:
已签署:
日期: 2023-11-24
Kenya Power TITLE: DISTRIBUTION TRANSFORMERS Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 14 of 50
"Note: KPLC will inspect and/or test built-up winding for its quality, weight of copper or aluminum, insulation materials properties and overall weight of coil assembly. The size of conductor used for different windings shall also be checked during stage inspection to check the current density.
4.4.3. Insulating materials
4.4.3.1. The HV and LV windings shall be separated so as to allow for cooling and ease of repair. Insulating sleeves for the transformer tapping's shall be in crepe paper and inter layer insulation shall be in Kraft Paper/ cellulosic paper, press paper and/or crepe paper.
4.4.3.2. There shall be double layer enamel insulation for the copper winding conductor. The insulation shall be of class A with temperature class of 105^(@)C as per IEC 60085.
4.4.3.3. Physical and electrical properties of insulation materials shall be as follows:
a) Press paper
Press paper shall be either a Grade K Thermally Upgraded Press paper or Grade K T/U diamond dotted press-paper (thermopox).
(i) Grade K Thermally Upgraded Press paper
Grade K Thermally Upgraded Press paper shall be made of sulphate wood pulp and used mainly as a layer insulating paper in low voltage and high voltage windings of oil immersed distribution transformers. Thermally upgraded paper is a cellulose based paper that has been chemically modified to reduce the rate at which the paper decomposes. Thermally upgraded paper shall be able to retain a much higher tensile and bursting strength than untreated papers when exposed to elevated temperatures. The technical characteristics shown in Table 3 shall be as per IEC 60641-2 and IEC 60243-1.
(ii) Grade K - Diamond dotted press paper - Electrical insulating press papers with Bstage resin dots
Grade K T/U diamond dotted press-paper (thermopox) is a press paper with qualities to improve the mechanical strength of oil immersed transformer windings without reducing partial discharge levels in accordance with IEC Standards 60641-2 and 60243-1.
b) Crepe paper"
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023-11-24 | Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 14 of 50 | |
| Note: KPLC will inspect and/or test built-up winding for its quality, weight of copper or aluminum, insulation materials properties and overall weight of coil assembly. The size of conductor used for different windings shall also be checked during stage inspection to check the current density. <br> 4.4.3. Insulating materials <br> 4.4.3.1. The HV and LV windings shall be separated so as to allow for cooling and ease of repair. Insulating sleeves for the transformer tapping's shall be in crepe paper and inter layer insulation shall be in Kraft Paper/ cellulosic paper, press paper and/or crepe paper. <br> 4.4.3.2. There shall be double layer enamel insulation for the copper winding conductor. The insulation shall be of class A with temperature class of $105^{\circ} \mathrm{C}$ as per IEC 60085. <br> 4.4.3.3. Physical and electrical properties of insulation materials shall be as follows: <br> a) Press paper <br> Press paper shall be either a Grade K Thermally Upgraded Press paper or Grade K T/U diamond dotted press-paper (thermopox). <br> (i) Grade K Thermally Upgraded Press paper <br> Grade K Thermally Upgraded Press paper shall be made of sulphate wood pulp and used mainly as a layer insulating paper in low voltage and high voltage windings of oil immersed distribution transformers. Thermally upgraded paper is a cellulose based paper that has been chemically modified to reduce the rate at which the paper decomposes. Thermally upgraded paper shall be able to retain a much higher tensile and bursting strength than untreated papers when exposed to elevated temperatures. The technical characteristics shown in Table 3 shall be as per IEC 60641-2 and IEC 60243-1. <br> (ii) Grade K - Diamond dotted press paper - Electrical insulating press papers with Bstage resin dots <br> Grade K T/U diamond dotted press-paper (thermopox) is a press paper with qualities to improve the mechanical strength of oil immersed transformer windings without reducing partial discharge levels in accordance with IEC Standards 60641-2 and 60243-1. <br> b) Crepe paper | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | |
| Signed: | | Signed: | |
| Date: 2023-11-24 | | | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
Issuc No.
7
修订编号
0
发行日期
2023-01-24
第 15 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issuc No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 15 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issuc No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 15 of 50 | |
Issued by: Head of Section, Standard devetopment Authorized by: Head of Department, Standards
Signed: Jeduy, Signed:
Date: 2023-21-24 Date: 2023-01-24| Issued by: Head of Section, Standard devetopment | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: Jeduy, | Signed: |
| Date: $2023-21-24$ | Date: 2023-01-24 |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装式三相油式配电变压器-规格 .
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer-Specification .| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer-Specification . |
文件 No.
KPl/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 16 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer-Specification ." Doc. No. KPl/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 16 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer-Specification . | Doc. No. | KPl/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 16 of 50 | |
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023-01-24 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: | Signed: |
| Date: 2023-01-24 | Date: 2023-01-24 |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORAIERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORAIERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 17 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORAIERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 17 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORAIERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 17 of 50 | |
Material with high permeability as per IEC 60404-8-7
Nominal Thickness Maximum specific total loss at 50 Hz
mm W/kg
0.23 0.90 to 1.00
Domain-refined material
Nominal Thickness Maximum specific total loss at J=1.7T at 50 Hz
mm W/kg
0.23 0.80 to 0.90| Material with high permeability as per IEC 60404-8-7 | |
| :--- | :--- |
| Nominal Thickness | Maximum specific total loss at 50 Hz |
| mm | W/kg |
| 0.23 | 0.90 to 1.00 |
| Domain-refined material | |
| Nominal Thickness | Maximum specific total loss at $\mathrm{J}=1.7 \mathrm{~T}$ at 50 Hz |
| mm | W/kg |
| 0.23 | 0.80 to 0.90 |
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
Dac.编号
KP1/13D/13/TSP/10/001-02
问题编号 .
7
修订编号
0
发行日期
2023-01-24
第 18 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Dac. No. KP1/13D/13/TSP/10/001-02
Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 18 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Dac. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No . | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 18 of 50 | |
4.6.1.7.铁芯必须用金属 U 型低碳钢夹具或横臂有效夹紧,并配有铁芯吊耳。在出厂验收测试中,制造商必须通过实验或先前的测试报告证明,支撑变压器绕组和铁芯的整个结构框架绝对能够承受变压器的反复短路。所有用于支撑铁芯的型钢在切割、钻孔和焊接后都必须进行彻底的喷砂或喷丸处理,然后再喷漆。任何非磁性或高电阻合金都必须是经确认和批准的优质合金。
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed:
Date: 2023-01/24 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: | |
| Date: 2023-01/24 | Date: 2023-01-24 |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号 .
7
修订编号
0
发行日期
2023-01-24
第 19 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 19 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No . | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 19 of 50 | |
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
"Signed:
Date: 2023-01-24" "Signed:
Date: 2023-01-24"
| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: <br> Date: 2023-01-24 | Signed: <br> Date: 2023-01-24 |
| | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
NOTE: Tenderers shall state losses both for nominal tap and extreme taps in the GTPs.
4.8. Capitalization
4.8.1. Transformer losses shall be capitalized at the following rates to facilitate evaluation and comparison of tenders. Loss capitalization shall be as per Table 7.
Table 7: Loss Capitalization
4.8.2 Losses will be capitalized at the above rates and added to the bid price according to the formula below:
Gep=Gbp+G($), where Gep= Bid evaluation price, Gbp= Bid price and
G($)= Adjustment for the cost of the operation and maintenance for 25 years (all in US Dollars) G($) is obtained by using the following formula:
G($)= US$ 2577 X {Total load losses, ONAF rating (copper loss + stray loss) at rated current at 75^(@)C in KW}+ US$ 4339 X {Total no load losses in KW (core loss + dielectric loss) }.| NOTE: Tenderers shall state losses both for nominal tap and extreme taps in the GTPs. |
| :--- |
| 4.8. Capitalization |
| 4.8.1. Transformer losses shall be capitalized at the following rates to facilitate evaluation and comparison of tenders. Loss capitalization shall be as per Table 7. |
| Table 7: Loss Capitalization |
| 4.8.2 Losses will be capitalized at the above rates and added to the bid price according to the formula below: |
| $\mathrm{Gep}=\mathrm{Gbp}+\mathrm{G}(\$)$, where $\mathrm{Gep}=$ Bid evaluation price, $\mathrm{Gbp}=$ Bid price and |
| $G(\$)=$ Adjustment for the cost of the operation and maintenance for 25 years (all in US Dollars) $G(\$)$ is obtained by using the following formula: |
| $\mathrm{G}(\$)=$ US$ 2577 X {Total load losses, ONAF rating (copper loss + stray loss) at rated current at $75^{\circ} \mathrm{C}$ in KW$\}+$ US$ 4339 X {Total no load losses in KW (core loss + dielectric loss) }. |
发布者标准制定科科长
授权人:标准部主任
已签署:
已签署:
Kenya Power "TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 20 of 50
Table 6: Sound Power Level, No-load and Full Load Losses at 75^(@)C
Sound power level (LWA), dB(A) Total Losses (No Load +Load losses) at 75^(@)C, Watts
Rating KVA No-load Losses, Watts Load losses) at 75^(@)C, Watts
11//0.420kV Transformers 50 48 90 750 840
100 51 145 1250 1395
200 55 310 2375 2685
315 56 440 3250 3690
33//0.420kV Transformers 50 48 160 1050 1210
100 51 293 1570 1863
200 55 530 2520 3050
315 56 672 3820 4492
"NOTE: Tenderers shall state losses both for nominal tap and extreme taps in the GTPs.
4.8. Capitalization
4.8.1. Transformer losses shall be capitalized at the following rates to facilitate evaluation and comparison of tenders. Loss capitalization shall be as per Table 7.
Table 7: Loss Capitalization
4.8.2 Losses will be capitalized at the above rates and added to the bid price according to the formula below:
Gep=Gbp+G($), where Gep= Bid evaluation price, Gbp= Bid price and
G($)= Adjustment for the cost of the operation and maintenance for 25 years (all in US Dollars) G($) is obtained by using the following formula:
G($)= US$ 2577 X {Total load losses, ONAF rating (copper loss + stray loss) at rated current at 75^(@)C in KW}+ US$ 4339 X {Total no load losses in KW (core loss + dielectric loss) }."
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed: https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-20.jpg?height=72&width=359&top_left_y=2401&top_left_x=1240
| Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- | :--- | :--- |
| | | | | Issue No. | 7 |
| | | | | Revision No. | 0 |
| | | | | Date of Issue | 2023-01-24 |
| | | | | Page 20 of 50 | |
| Table 6: Sound Power Level, No-load and Full Load Losses at $75^{\circ} \mathrm{C}$ | | | | | |
| | | Sound power level (LWA), dB(A) | | | Total Losses (No Load +Load losses) at $75^{\circ} \mathrm{C}$, Watts |
| | Rating KVA | | No-load Losses, Watts | Load losses) at $75^{\circ} \mathrm{C}$, Watts | |
| $11 / 0.420 \mathrm{kV}$ Transformers | 50 | 48 | 90 | 750 | 840 |
| | 100 | 51 | 145 | 1250 | 1395 |
| | 200 | 55 | 310 | 2375 | 2685 |
| | 315 | 56 | 440 | 3250 | 3690 |
| $33 / 0.420 \mathrm{kV}$ Transformers | 50 | 48 | 160 | 1050 | 1210 |
| | 100 | 51 | 293 | 1570 | 1863 |
| | 200 | 55 | 530 | 2520 | 3050 |
| | 315 | 56 | 672 | 3820 | 4492 |
| NOTE: Tenderers shall state losses both for nominal tap and extreme taps in the GTPs. <br> 4.8. Capitalization <br> 4.8.1. Transformer losses shall be capitalized at the following rates to facilitate evaluation and comparison of tenders. Loss capitalization shall be as per Table 7. <br> Table 7: Loss Capitalization <br> 4.8.2 Losses will be capitalized at the above rates and added to the bid price according to the formula below: <br> $\mathrm{Gep}=\mathrm{Gbp}+\mathrm{G}(\$)$, where $\mathrm{Gep}=$ Bid evaluation price, $\mathrm{Gbp}=$ Bid price and <br> $G(\$)=$ Adjustment for the cost of the operation and maintenance for 25 years (all in US Dollars) $G(\$)$ is obtained by using the following formula: <br> $\mathrm{G}(\$)=$ US$ 2577 X {Total load losses, ONAF rating (copper loss + stray loss) at rated current at $75^{\circ} \mathrm{C}$ in KW$\}+$ US$ 4339 X {Total no load losses in KW (core loss + dielectric loss) }. | | | | | |
| | | | | | | | | |
| | | | | | | | | |
| | | | | | | | | |
| | | | | | | | | |
| | | | | | | | | |
| Issued by: Head of Section, Standard development | | | Authorized by: Head of Department, Standards | | |
| Signed: | | | Signed: |  | |
| | | | | | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KPl/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 21 页,共 50 页
Kenya Power "TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KPl/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 21 of 50 | Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KPl/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 21 of 50 | |
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-011-24
第 22 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-011-24
Page 22 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-011-24 |
| | | Page 22 of 50 | |
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023- 0424 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: | Signed: |
| Date: 2023- 0424 | Date: 2023-01-24 |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 23 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 23 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 23 of 50 | |
4.10.净空
4.10.1.外部净空
4.10.1.1.完全组装后,如在使用中,空气中的电气间隙必须足以承受指定的脉冲耐压试验电压。
4.10.1.2.应注意确保所有配件/附件的位置适当,不影响与套管终端的外部连接和间隙。
4.10.1.3.最小外部空气间隙(安装接线夹时)应如表 9 所示。
表 9:空气中的外部间隙(根据 IEC 标准 60076)
相位中心之间的标称系统电压
LV
11 千伏
33 千伏
相地和相中的最小间隙
毫米
80
150
380
同一绕组相与相之间的最小间隙
毫米
80
150
380
高压相带电部分与低压相带电部分之间的最小间隙
毫米
-
150
380
最小爬电距离
毫米
60
372
1116
Nominal System Voltage between Phases Centers LV 11 kV 33 kV
Minimum clearance phase-to-earth and phase-to-neutral mm 80 150 380
Minimum clearance phase-to-phase between phases of the same winding mm 80 150 380
Minimum clearance between live part of HV phase to live part of LV phase mm - 150 380
Minimum creepage distance mm 60 372 1116| Nominal System Voltage between Phases Centers | | LV | 11 kV | 33 kV |
| :--- | :--- | :--- | :--- | :--- |
| Minimum clearance phase-to-earth and phase-to-neutral | mm | 80 | 150 | 380 |
| Minimum clearance phase-to-phase between phases of the same winding | mm | 80 | 150 | 380 |
| Minimum clearance between live part of HV phase to live part of LV phase | mm | - | 150 | 380 |
| Minimum creepage distance | mm | 60 | 372 | 1116 |
Description 11 kV 33 kV
Minimum radial clearance of LV coil and core Mm 3 3
Minimum radial clearance of LV coil and earth Mm 3 3
Minimum radial clearance between LV and HV Mm 8 20
Minimum electrical clearance between the surface of the tank, tapping leads and edges of winding mm 15 30
Minimum radial clearance between HV and HV windings mm 8 20| Description | | 11 kV | 33 kV |
| :--- | :--- | :--- | :--- |
| Minimum radial clearance of LV coil and core | Mm | 3 | 3 |
| Minimum radial clearance of LV coil and earth | Mm | 3 | 3 |
| Minimum radial clearance between LV and HV | Mm | 8 | 20 |
| Minimum electrical clearance between the surface of the tank, tapping leads and edges of winding | mm | 15 | 30 |
| Minimum radial clearance between HV and HV windings | mm | 8 | 20 |
发布者标准制定科科长
授权人:标准部主任
签名: pedy)
已签署:
日期:2023-0124
日期: 2023-01-24
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: pedy) Signed:
Date: 2023-0124 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: pedy) | Signed: |
| Date: 2023-0124 | Date: 2023-01-24 |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 24 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 24 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 24 of 50 | |
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed:
Date: 2023-13-24 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: | |
| Date: 2023-13-24 | Date: 2023-01-24 |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
4.12.4.
The tank shall be complete with lifting lugs suitable for lifting the complete transformer with oil. The lifting lugs shall be welded on the side walls and shall be heavy duty type made of suitable grade of steel plate of at least 8 mm thick and shall be reinforced with a factor of safety of at least 2 (based on weight of complete transformer filled with oil).| 4.12.4. |
| :--- |
| The tank shall be complete with lifting lugs suitable for lifting the complete transformer with oil. The lifting lugs shall be welded on the side walls and shall be heavy duty type made of suitable grade of steel plate of at least 8 mm thick and shall be reinforced with a factor of safety of at least 2 (based on weight of complete transformer filled with oil). |
4.12.6.
Top tank cover shall be of such a design and construction as to prevent accumulation of water and shall be bolted to the flange on the tank top to form a weatherproof joint. The top cover fixing shall be with hot dip galvanized steel bolts and synthetic rubber-and-cork composition gasket of 6 mm minimum thickness. The bolts shall each have two flat washers and one spring washer.| 4.12.6. |
| :--- |
| Top tank cover shall be of such a design and construction as to prevent accumulation of water and shall be bolted to the flange on the tank top to form a weatherproof joint. The top cover fixing shall be with hot dip galvanized steel bolts and synthetic rubber-and-cork composition gasket of 6 mm minimum thickness. The bolts shall each have two flat washers and one spring washer. |
4.13.1.
External and internal surfaces of all transformer tanks and other fabricated steel items shall be cleaned of scale, rust and surface dirt by shot blast cleaning or other suitable approved method. After cleaning, these surfaces should be immediately covered with paint.| 4.13.1. |
| :--- |
| External and internal surfaces of all transformer tanks and other fabricated steel items shall be cleaned of scale, rust and surface dirt by shot blast cleaning or other suitable approved method. After cleaning, these surfaces should be immediately covered with paint. |
Kenya Power "TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 25 of 50
accordance with relevant ISO standards. A copy of the certificate shall be submitted with the transformers during delivery to KPLC stores.
"4.12.4.
The tank shall be complete with lifting lugs suitable for lifting the complete transformer with oil. The lifting lugs shall be welded on the side walls and shall be heavy duty type made of suitable grade of steel plate of at least 8 mm thick and shall be reinforced with a factor of safety of at least 2 (based on weight of complete transformer filled with oil)."
4.12.5. Steel radiators (corrugations) of adequate thickness to deter oil vandalism shall be used for cooling. The transformer shall be capable of giving continuous rated output without exceeding the specified temperature rise.
"4.12.6.
Top tank cover shall be of such a design and construction as to prevent accumulation of water and shall be bolted to the flange on the tank top to form a weatherproof joint. The top cover fixing shall be with hot dip galvanized steel bolts and synthetic rubber-and-cork composition gasket of 6 mm minimum thickness. The bolts shall each have two flat washers and one spring washer."
4.12.7. The top cover bolts shall include at least four (4) non-standard bolts of dome shaped head with non-standard profile and that can't be opened by use of standard Allen-screws, pipe wrenches, spanners etc. to deter un-authorized opening. One (1) piece of the key/tool for every twenty (20) transformers for opening the special bolts shall be provided to Kenya Power during delivery. They shall be delivered to Electrical Plant Transformer Workshop, Isiolo Road, Nairobi.
4.12.8. Provision shall be made in form of a removable jumper, to provide for good electrical connection between the top cover and the transformer tank. The jumper shall be sufficiently rated to carry the fault currents without damage. It shall be of tinned copper strip 25mmxx1.2mm and shall be secured by stainless steel bolt & nut.
4.13. Paint Work
"4.13.1.
External and internal surfaces of all transformer tanks and other fabricated steel items shall be cleaned of scale, rust and surface dirt by shot blast cleaning or other suitable approved method. After cleaning, these surfaces should be immediately covered with paint."
4.13.2. The exterior shall be thoroughly cleaned by shot blasting or other approved method and given priming coat/ epoxy painting followed by two coats of contrasting colours of durable weather-resisting paint. The final colour of the exterior surfaces shall be Dark Admiralty
Issued by: Head of Section, Standard development
Signed: Signed:
Date: 2023-91-24 Date: 2023-01-24 | Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No . | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 25 of 50 | |
| accordance with relevant ISO standards. A copy of the certificate shall be submitted with the transformers during delivery to KPLC stores. | | | |
| 4.12.4. <br> The tank shall be complete with lifting lugs suitable for lifting the complete transformer with oil. The lifting lugs shall be welded on the side walls and shall be heavy duty type made of suitable grade of steel plate of at least 8 mm thick and shall be reinforced with a factor of safety of at least 2 (based on weight of complete transformer filled with oil). | | | |
| 4.12.5. Steel radiators (corrugations) of adequate thickness to deter oil vandalism shall be used for cooling. The transformer shall be capable of giving continuous rated output without exceeding the specified temperature rise. | | | |
| 4.12.6. <br> Top tank cover shall be of such a design and construction as to prevent accumulation of water and shall be bolted to the flange on the tank top to form a weatherproof joint. The top cover fixing shall be with hot dip galvanized steel bolts and synthetic rubber-and-cork composition gasket of 6 mm minimum thickness. The bolts shall each have two flat washers and one spring washer. | | | |
| 4.12.7. The top cover bolts shall include at least four (4) non-standard bolts of dome shaped head with non-standard profile and that can't be opened by use of standard Allen-screws, pipe wrenches, spanners etc. to deter un-authorized opening. One (1) piece of the key/tool for every twenty (20) transformers for opening the special bolts shall be provided to Kenya Power during delivery. They shall be delivered to Electrical Plant Transformer Workshop, Isiolo Road, Nairobi. | | | |
| 4.12.8. Provision shall be made in form of a removable jumper, to provide for good electrical connection between the top cover and the transformer tank. The jumper shall be sufficiently rated to carry the fault currents without damage. It shall be of tinned copper strip $25 \mathrm{~mm} \times 1.2 \mathrm{~mm}$ and shall be secured by stainless steel bolt $\&$ nut. | | | |
| 4.13. Paint Work | | | |
| 4.13.1. <br> External and internal surfaces of all transformer tanks and other fabricated steel items shall be cleaned of scale, rust and surface dirt by shot blast cleaning or other suitable approved method. After cleaning, these surfaces should be immediately covered with paint. | | | |
| 4.13.2. The exterior shall be thoroughly cleaned by shot blasting or other approved method and given priming coat/ epoxy painting followed by two coats of contrasting colours of durable weather-resisting paint. The final colour of the exterior surfaces shall be Dark Admiralty | | | |
| Issued by: Head of Section, Standard development | | | |
| Signed: | | Signed: | |
| Date: 2023-91-24 | Date: 2023-01-24 | | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
编号不
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 27 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Dos. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 27 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Dos. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 27 of 50 | |
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023-0才-24 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: | Signed: |
| Date: 2023-0才-24 | Date: 2023-01-24 |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
LV clamp connectors shall be made of tinned copper alloy (brass, bronze or phosphor bronze). The tin coating thickness shall be 25 mum.
g) Thermometer pocket to be used during temperature rise test.
h) Surge arrester mounting brackets as per clause 4.15
i) Arcing horns:
Arcing horns shall be provided on each HV bushings.| LV clamp connectors shall be made of tinned copper alloy (brass, bronze or phosphor bronze). The tin coating thickness shall be $25 \mu \mathrm{~m}$. |
| :--- |
| g) Thermometer pocket to be used during temperature rise test. |
| h) Surge arrester mounting brackets as per clause 4.15 |
| i) Arcing horns: |
| Arcing horns shall be provided on each HV bushings. |
Kenya Power "TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 28 of 50
"LV clamp connectors shall be made of tinned copper alloy (brass, bronze or phosphor bronze). The tin coating thickness shall be 25 mum.
g) Thermometer pocket to be used during temperature rise test.
h) Surge arrester mounting brackets as per clause 4.15
i) Arcing horns:
Arcing horns shall be provided on each HV bushings."
4.16.2. All fittings and accessories shall be designed and secured in such a manner that makes it impossible for vandals to siphon oil from the transformer even after forceful breakage of the fitting/accessory. There shall be no oil leaks from fittings and accessories.
4.16.3. Detailed drawings for the transformer (including internal details) and its components showing features that make it impossible for vandals to siphon oil from the transformer even after forceful breakage of the fitting/accessory shall be submitted to KPLC for approval before manufacture.
4.l6.4. The tank shall be equipped with mounting rails at the bottom which shall facilitate lifting with a forklift.
5. MARKING, LABELLING AND PACKING
5.1. The transformer and associated components shall be packed in a manner as to protect them from any damage in transportation and handling. The transformer shall first be mounted and bolted to wooden base blocks and then covered with a polythene cover. The transformer with the wooden base blocks shall then be secured tightly in the container to avoid transit movements.
5.2. The transformer shall be dispatched fully assembled, oil filled and complete with surge arrester mounting brackets fitted.
5.3. Each assembly and package of items associated with the transformer shall be suitably marked.
5.4. In addition to markings and labels required elsewhere in the specification, each transformer shall be provided with a rating and diagram plate of weatherproof material, fitted in a visible position, showing the appropriate details listed in clause 8 of IEC 60076-1:2011. The entries on the plate | Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 28 of 50 | |
| LV clamp connectors shall be made of tinned copper alloy (brass, bronze or phosphor bronze). The tin coating thickness shall be $25 \mu \mathrm{~m}$. <br> g) Thermometer pocket to be used during temperature rise test. <br> h) Surge arrester mounting brackets as per clause 4.15 <br> i) Arcing horns: <br> Arcing horns shall be provided on each HV bushings. | | | |
| 4.16.2. All fittings and accessories shall be designed and secured in such a manner that makes it impossible for vandals to siphon oil from the transformer even after forceful breakage of the fitting/accessory. There shall be no oil leaks from fittings and accessories. | | | |
| 4.16.3. Detailed drawings for the transformer (including internal details) and its components showing features that make it impossible for vandals to siphon oil from the transformer even after forceful breakage of the fitting/accessory shall be submitted to KPLC for approval before manufacture. | | | |
| 4.l6.4. The tank shall be equipped with mounting rails at the bottom which shall facilitate lifting with a forklift. | | | |
| 5. MARKING, LABELLING AND PACKING | | | |
| 5.1. The transformer and associated components shall be packed in a manner as to protect them from any damage in transportation and handling. The transformer shall first be mounted and bolted to wooden base blocks and then covered with a polythene cover. The transformer with the wooden base blocks shall then be secured tightly in the container to avoid transit movements. | | | |
| 5.2. The transformer shall be dispatched fully assembled, oil filled and complete with surge arrester mounting brackets fitted. | | | |
| 5.3. Each assembly and package of items associated with the transformer shall be suitably marked. | | | |
| 5.4. In addition to markings and labels required elsewhere in the specification, each transformer shall be provided with a rating and diagram plate of weatherproof material, fitted in a visible position, showing the appropriate details listed in clause 8 of IEC 60076-1:2011. The entries on the plate | | | |
标题:
Dac.编号
KP1/13D/13/TSP/10/001-02
配电变压器 第 2 部分:杆装式三相油式配电变压器--规范
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer-Specification| DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer-Specification |
问题编号
7
修订编号
0
发行日期
2023-01-24
第 29 页,共 50 页
须有不可磨灭的标记(蚀刻、雕刻或冲压),并须清晰可辨和具有永久性。
5.5.此外,额定值和图示牌还应包括最高、最低和原则分接位置的负载和空载损耗、绝缘温度等级、接线图和 "PROPERTY OF THE KENYA POWER AND LIGHTING CO.PLC "的字样,所有字样均应按 6.4 中的规定不可磨灭地清晰标出。
发布者标准制定科科长
授权人:标准部主任
已签署:
已签署:
日期: 2023-01-24
https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-29.jpg?height=195&width=225&top_left_y=132&top_left_x=329 TITLE: Dac. No. KP1/13D/13/TSP/10/001-02
"DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer-Specification" Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 29 of 50
shall be indelibly marked (either by etching, engraving or stamping) and shall be legible and permanent.
5.5. In addition, the rating and diagram plate shall include load and no-load losses for the highest, lowest and principle tap positions, temperature class of insulation, connection diagram and the inscription 'PROPERTY OF THE KENYA POWER AND LIGHTING CO. PLC' all marked indelibly and legibly as in 6.4.
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023-01-24 |  | TITLE: | Dac. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer-Specification | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 29 of 50 | |
| shall be indelibly marked (either by etching, engraving or stamping) and shall be legible and permanent. | | | |
| 5.5. In addition, the rating and diagram plate shall include load and no-load losses for the highest, lowest and principle tap positions, temperature class of insulation, connection diagram and the inscription 'PROPERTY OF THE KENYA POWER AND LIGHTING CO. PLC' all marked indelibly and legibly as in 6.4. | | | |
| | | | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | |
| Signed: | | Signed: | |
| Date: 2023-01-24 | | | |
肯尼亚电力公司
标题:
文件 No.
KPI/13D/13/TSP/10/001-02
配电变压器 第 2 部分:柱装式三相油式配电变压器 - 规格
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
问题编号
7
修订编号
0
发行日期
2023-01-24
第 30 页,共 50 页
Kenya Power TITLE: Doc. No. KPI/13D/13/TSP/10/001-02
"DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 30 of 50 | Kenya Power | TITLE: | Doc. No. | KPI/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 30 of 50 | |
shall not relieve the manufacturer from the responsibility of full compliance to the specification or rejection from non-compliance.
A.4. The transformer shall be subject to acceptance tests at the manufacturer's works before dispatch. Acceptance tests shall be witnessed by two Engineers appointed by KPLC and shall include the following:
A.4.1. Routine tests to IEC 60076 (to be done during acceptance testing at factory)
a) Measurement of winding resistance-clause 11.2
b) Measurement of voltage ration and check of Phase Displacement-Clause 11.2
c) Measurement of short circuit impedance and load loss-Clause 11.4
d) Measurement of no-load loss and current- Clause 11.5
e) Dielectric routine tests -IEC 60076-3
(i) Separate source voltage withstand test
(ii) Induced over-voltage
(iii)Insulation resistance
f) Leaking test with pressure for liquid immersed transformers (tightness test)-clause 11.8
g) Tests on off-load tap-changer - Mechanical tests as per IEC 60214-1
h) Check of core and frame insulation for liquid immersed transformers with core or frame Insulation-Clause 11.12
i) Any other test not listed above but specified by the latest edition of IEC 60076.
A.4.2 Type Tests to IEC 60076 (to be done on one unit during acceptance testing at factory)
a) Temperature rise test - To be performed on one unit during acceptance testing.
b) Lightning impulse withstand voltage test - To be performed on one unit during acceptance testing.
c) Measurement of no-load loss and current at 90% and 110% of rated voltage - To be performed on one unit during acceptance testing.
A.4.3 Additional tests (to be done on samples during acceptance testing at factory)| shall not relieve the manufacturer from the responsibility of full compliance to the specification or rejection from non-compliance. |
| :--- |
| A.4. The transformer shall be subject to acceptance tests at the manufacturer's works before dispatch. Acceptance tests shall be witnessed by two Engineers appointed by KPLC and shall include the following: |
| A.4.1. Routine tests to IEC 60076 (to be done during acceptance testing at factory) |
| a) Measurement of winding resistance-clause 11.2 |
| b) Measurement of voltage ration and check of Phase Displacement-Clause 11.2 |
| c) Measurement of short circuit impedance and load loss-Clause 11.4 |
| d) Measurement of no-load loss and current- Clause 11.5 |
| e) Dielectric routine tests -IEC 60076-3 |
| (i) Separate source voltage withstand test |
| (ii) Induced over-voltage |
| (iii)Insulation resistance |
| f) Leaking test with pressure for liquid immersed transformers (tightness test)-clause 11.8 |
| g) Tests on off-load tap-changer - Mechanical tests as per IEC 60214-1 |
| h) Check of core and frame insulation for liquid immersed transformers with core or frame Insulation-Clause 11.12 |
| i) Any other test not listed above but specified by the latest edition of IEC 60076. |
| A.4.2 Type Tests to IEC 60076 (to be done on one unit during acceptance testing at factory) |
| a) Temperature rise test - To be performed on one unit during acceptance testing. |
| b) Lightning impulse withstand voltage test - To be performed on one unit during acceptance testing. |
| c) Measurement of no-load loss and current at $90 \%$ and $110 \%$ of rated voltage - To be performed on one unit during acceptance testing. |
| A.4.3 Additional tests (to be done on samples during acceptance testing at factory) |
发布者标准制定科科长
授权人:标准部主任
已签署:
已签署:
日期:2023,41-24
日期: 2023-01-24
https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-31.jpg?height=177&width=214&top_left_y=183&top_left_x=288 TITLE: dISTRIBUTION TRANSFORNERS Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification Doc. No. KP1/13D/13/TSP/10/001-02
Issuc No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 31 of 50
"shall not relieve the manufacturer from the responsibility of full compliance to the specification or rejection from non-compliance.
A.4. The transformer shall be subject to acceptance tests at the manufacturer's works before dispatch. Acceptance tests shall be witnessed by two Engineers appointed by KPLC and shall include the following:
A.4.1. Routine tests to IEC 60076 (to be done during acceptance testing at factory)
a) Measurement of winding resistance-clause 11.2
b) Measurement of voltage ration and check of Phase Displacement-Clause 11.2
c) Measurement of short circuit impedance and load loss-Clause 11.4
d) Measurement of no-load loss and current- Clause 11.5
e) Dielectric routine tests -IEC 60076-3
(i) Separate source voltage withstand test
(ii) Induced over-voltage
(iii)Insulation resistance
f) Leaking test with pressure for liquid immersed transformers (tightness test)-clause 11.8
g) Tests on off-load tap-changer - Mechanical tests as per IEC 60214-1
h) Check of core and frame insulation for liquid immersed transformers with core or frame Insulation-Clause 11.12
i) Any other test not listed above but specified by the latest edition of IEC 60076.
A.4.2 Type Tests to IEC 60076 (to be done on one unit during acceptance testing at factory)
a) Temperature rise test - To be performed on one unit during acceptance testing.
b) Lightning impulse withstand voltage test - To be performed on one unit during acceptance testing.
c) Measurement of no-load loss and current at 90% and 110% of rated voltage - To be performed on one unit during acceptance testing.
A.4.3 Additional tests (to be done on samples during acceptance testing at factory)"
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023,41-24 Date: 2023-01-24 |  | TITLE: dISTRIBUTION TRANSFORNERS Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issuc No . | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 31 of 50 | |
| shall not relieve the manufacturer from the responsibility of full compliance to the specification or rejection from non-compliance. <br> A.4. The transformer shall be subject to acceptance tests at the manufacturer's works before dispatch. Acceptance tests shall be witnessed by two Engineers appointed by KPLC and shall include the following: <br> A.4.1. Routine tests to IEC 60076 (to be done during acceptance testing at factory) <br> a) Measurement of winding resistance-clause 11.2 <br> b) Measurement of voltage ration and check of Phase Displacement-Clause 11.2 <br> c) Measurement of short circuit impedance and load loss-Clause 11.4 <br> d) Measurement of no-load loss and current- Clause 11.5 <br> e) Dielectric routine tests -IEC 60076-3 <br> (i) Separate source voltage withstand test <br> (ii) Induced over-voltage <br> (iii)Insulation resistance <br> f) Leaking test with pressure for liquid immersed transformers (tightness test)-clause 11.8 <br> g) Tests on off-load tap-changer - Mechanical tests as per IEC 60214-1 <br> h) Check of core and frame insulation for liquid immersed transformers with core or frame Insulation-Clause 11.12 <br> i) Any other test not listed above but specified by the latest edition of IEC 60076. <br> A.4.2 Type Tests to IEC 60076 (to be done on one unit during acceptance testing at factory) <br> a) Temperature rise test - To be performed on one unit during acceptance testing. <br> b) Lightning impulse withstand voltage test - To be performed on one unit during acceptance testing. <br> c) Measurement of no-load loss and current at $90 \%$ and $110 \%$ of rated voltage - To be performed on one unit during acceptance testing. <br> A.4.3 Additional tests (to be done on samples during acceptance testing at factory) | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | |
| Signed: | Signed: | | |
| Date: 2023,41-24 | Date: 2023-01-24 | | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器 - 规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonner - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonner - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 32 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonner - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 32 of 50
| Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonner - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 32 of 50 | |
| | | | |
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-32.jpg?height=73&width=262&top_left_y=2397&top_left_x=225 https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-32.jpg?height=63&width=572&top_left_y=2397&top_left_x=1076
Date: 2023-0 -24 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
|  |  |
| Date: 2023-0 -24 | Date: 2023-01-24 |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 33 页,共 50 页
Kenya Power "TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 33 of 50
| Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 33 of 50 | |
| | | | |
附录 C:技术文件(规范性文件)
C.1.投标人应提交附件 AA (保证技术细节)所要求的完整技术文件,以供评标。为评标而提交的文件(均为英文)应包括以下内容:
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号 .
7
修订编号
0
发行日期
2023-01-24
第 34 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 34 of 50
| Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No . | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 34 of 50 | |
| | | | |
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KPl/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 35 页,共 50 页
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KPl/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 35 of 50 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KPl/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 35 of 50 | |
范围: a) 按照规格和合同条款,设计、制造、测试、装运并向 KPLC 仓库/现场交付杆式单相配电变压器。 b) 确保在为 KPLC 制造变压器时,设计充分、工艺精良、工程操作规范良好,并遵守标准、规格和适用法规。
Scope: a) Design, manufacture, test, ship and deliver pole-mounted single phase distribution transformer to KPLC store/site as per specification and terms of contract.
b) Ensure adequacy of the design, good workmanship, good engineering practice and adherence to standards, specifications and applicable regulations in the manufacture of the transformers for KPLC| Scope: a) Design, manufacture, test, ship and deliver pole-mounted single phase distribution transformer to KPLC store/site as per specification and terms of contract. |
| :--- |
| b) Ensure adequacy of the design, good workmanship, good engineering practice and adherence to standards, specifications and applicable regulations in the manufacture of the transformers for KPLC |
2
适用标准
3
术语和定义
4.1.1
运行服务条件(包括海拔高度、温度范围、湿度、污染和等气压水平)
Clause Number Description (Indicate KVA and Voltage ratings in the columns on the right) BIDDER'S OFFER
50KVA lIKV OR 33kV 100KVA 11KV OR 33KV 200KVA 11KV OR 33KV 315KVA 11KV OR 33 KV
- Name and address of the Manufacturer
Country of manufacture
Manufacturer's Letter of Authorization
Model/Type Reference No. of the offered transformer
Manufacturer's warranty and guarantee for the offered transformer
1. "Scope: a) Design, manufacture, test, ship and deliver pole-mounted single phase distribution transformer to KPLC store/site as per specification and terms of contract.
b) Ensure adequacy of the design, good workmanship, good engineering practice and adherence to standards, specifications and applicable regulations in the manufacture of the transformers for KPLC"
2 Applicable Standards
3 Terms and Definitions
4.1.1 Operating Service Conditions (Include altitude, temperature range, humidity, pollution and isokeraunic level) | Clause Number | Description (Indicate KVA and Voltage ratings in the columns on the right) | BIDDER'S OFFER | | | |
| :--- | :--- | :--- | :--- | :--- | :--- |
| | | 50KVA lIKV OR 33kV | 100KVA 11KV OR 33KV | 200KVA 11KV OR 33KV | 315KVA 11KV OR 33 KV |
| - | Name and address of the Manufacturer | | | | |
| | Country of manufacture | | | | |
| | Manufacturer's Letter of Authorization | | | | |
| | Model/Type Reference No. of the offered transformer | | | | |
| | Manufacturer's warranty and guarantee for the offered transformer | | | | |
| 1. | Scope: a) Design, manufacture, test, ship and deliver pole-mounted single phase distribution transformer to KPLC store/site as per specification and terms of contract. <br> b) Ensure adequacy of the design, good workmanship, good engineering practice and adherence to standards, specifications and applicable regulations in the manufacture of the transformers for KPLC | | | | |
| 2 | Applicable Standards | | | | |
| 3 | Terms and Definitions | | | | |
| 4.1.1 | Operating Service Conditions (Include altitude, temperature range, humidity, pollution and isokeraunic level) | | | | |
发布者标准制定科科长
授权人:标准部主任
已签署:
已签署:
日期:2023-0124
日期: 2023-01-24
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023-0124 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: | Signed: |
| Date: 2023-0124 | Date: 2023-01-24 |
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号 .
7
修订编号
0
发行日期
2023-01-24
第 36 页,共 50 页
4.1.2.1 至 4.1.2.3
4.1.2.1 to
4.1.2.3| 4.1.2.1 to |
| :--- |
| 4.1.2.3 |
"TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 36 of 50
"4.1.2.1 to
4.1.2.3" System Characteristics
4.2 General Requirements
4.2.1 Outdoor, oil type, ONAN and core type
4.2.2 Design Service Life
"4.2 .3
4.2.4" Two winding, three phase integral unit
Type of transformer offered
4.2.4.1 Hermetically sealed, with allowance for oil expansion
Active parts submerged in oil and provision for oil expansion
4.2.4.2 Free breathing type, conservator with cobalt free dehydrating breather and oil gauge
4.2 .5 Design to facilitate operation, inspection, maintenance & repairs
To carry loading beyond rated power as per IEC 60076-7
4.2 .6 Safety & Regulatory Requirements
4.2.7 No water pockets, rain water do not collect on top cover with 10 mm overlap to conceal gasket
To avoid seepage of water into the tank, all bushings and any other fitting on top cover shall either be inclined or bevelled such that they are raised by a minimum 3 mm from the surface of the top cover
"4.2.8
4.2.9" Corresponding parts to be interchangeable
Fittings & accessories secured from inside or have small openings that do not allow oil siphoning
4.2.10 Test certificate for transformer components and materials-Attach for verification
4.2.11 All connections & contacts of ample section and surface for required currents
lssued by: Head of Section, Standard development Authorized by: Head of Department, Standards
"Signed:
Date: 2023.01至" Signed:
Date: 2023-01-24 | | | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | | | Issue No . | 7 | | |
| | | | Revision No. | 0 | | |
| | | | Date of Issue | 2023-01-24 | | |
| | | | Page 36 of 50 | | | |
| 4.1.2.1 to <br> 4.1.2.3 | System Characteristics | | | | | |
| | | | | | | |
| 4.2 | General Requirements | | | | | |
| 4.2.1 | Outdoor, oil type, ONAN and core type | | | | | |
| 4.2.2 | Design Service Life | | | | | |
| 4.2 .3 <br> 4.2.4 | Two winding, three phase integral unit | | | | | |
| | Type of transformer offered | | | | | |
| 4.2.4.1 | Hermetically sealed, with allowance for oil expansion | | | | | |
| | Active parts submerged in oil and provision for oil expansion | | | | | |
| 4.2.4.2 | Free breathing type, conservator with cobalt free dehydrating breather and oil gauge | | | | | |
| 4.2 .5 | Design to facilitate operation, inspection, maintenance & repairs | | | | | |
| | To carry loading beyond rated power as per IEC 60076-7 | | | | | |
| 4.2 .6 | Safety & Regulatory Requirements | | | | | |
| 4.2.7 | No water pockets, rain water do not collect on top cover with 10 mm overlap to conceal gasket | | | | | |
| | To avoid seepage of water into the tank, all bushings and any other fitting on top cover shall either be inclined or bevelled such that they are raised by a minimum 3 mm from the surface of the top cover | | | | | |
| 4.2.8 <br> 4.2.9 | Corresponding parts to be interchangeable | | | | | |
| | Fittings & accessories secured from inside or have small openings that do not allow oil siphoning | | | | | |
| 4.2.10 | Test certificate for transformer components and materials-Attach for verification | | | | | |
| 4.2.11 | All connections & contacts of ample section and surface for required currents | | | | | |
| lssued by: Head of Section, Standard development | | | Authorized by: Head of Department, Standards | | | |
| Signed: <br> Date: 2023.01至 | | | Signed: | | | |
| | | | Date: 2023-01-24 | | | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
Issuc No .
7
修订编号
0
发行日期
2023-01-24
第 37 页,共 50 页
载流部件中的所有螺栓和螺母必须由含铜量至少 70% 的黄铜制成
4.2.12
4.2.13
4.2.12
4.2.13| 4.2.12 |
| :--- |
| 4.2.13 |
所用材料不会导致油品酸化
最大噪声级的状态值(NEMA TR.1)
4.2.14
可承受超过重力加速度 1 g 的运输能力
4.2.15
适合杆式安装,底座下有钢槽
4.2.16
提供的变压器图纸
变压器外形尺寸(长、宽、高)(毫米
4.2.17a) 至 g)
设计图纸需在生产前获得批准
变压器的整体尺寸和相关电气间隙。这应包括所有角度和各自角度:
a) 油的重量
b) 低压绕组导线的重量
c) 高压绕组导线重量
- d) 核心材料
e) 铜质绕组材料
f) 绝缘材料
g) 钢制水箱/核心夹结构
铁芯/线圈/隔热材料尺寸、间隙(内部和外部)以及堆叠/线圈绕组顺序详情
按比例绘制铭牌
衬套、有载分接开关和夹具的尺寸图
在所有技术工程图纸的图例上标明制造商名称、标识、型号、修订版/图纸编号和密钥
弧形犄角详图
签发人: 标准制定科科长标准制定科科长 授权人: 标准制定部主任部门负责人,标准
Issued by: Head of Section, Standard development
Authorized by: Head of Department, Standards| Issued by: Head of Section, Standard development |
| :--- |
| Authorized by: Head of Department, Standards |
已签名: qquad\qquad
日期: 2023-01-24
日期: 2023-01-24
Kenya Power "TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issuc No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 37 of 50
All bolts and nuts in current carrying parts shall be made of brass with at least 70% copper content
"4.2.12
4.2.13" Materials used do not lead to acidity in oil
State values of maximum noise level (NEMA TR.1)
4.2.14 Transport to withstand 1 g beyond gravitational acceleration
4.2.15 Suitable for pole mounting, steel channel under base
4.2.16 Drawings of offered transformer
Overall dimensions of offered transformer (length, width & height) in mm
4.2.17a) to g) Design drawings for approval before manufacture
Overall dimensions of the transformer and relevant electrical clearances. This shall include all perspectives and respective:
a) Weight of oil
b) Weight of LV winding conductor
c) Weight of HV winding conductor
- d) Core material
e) Copper winding material
f) Insulating material
g) Steel tank/core clamp structure
Core/coil/insulation dimensions, clearances (internal and external) and stacking/coil winding sequence detail
Drawing of nameplate to scale
Dimensional drawings of bushings, tapchanger and clamps
Legend tor all technical engineering drawings with manufacturers name, logo, model number, revision/drawing number and key
Detailed drawing of arcing horns
"Issued by: Head of Section, Standard development
Authorized by: Head of Department, Standards"
Signed: qquad
Date: 2023-01-24 Date: 2023-01-24 | Kenya Power | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issuc No . | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 37 of 50 | |
| | All bolts and nuts in current carrying parts shall be made of brass with at least 70% copper content | | |
| 4.2.12 <br> 4.2.13 | Materials used do not lead to acidity in oil | | |
| | State values of maximum noise level (NEMA TR.1) | | |
| 4.2.14 | Transport to withstand 1 g beyond gravitational acceleration | | |
| 4.2.15 | Suitable for pole mounting, steel channel under base | | |
| 4.2.16 | Drawings of offered transformer | | |
| | Overall dimensions of offered transformer (length, width & height) in mm | | |
| 4.2.17a) to g) | Design drawings for approval before manufacture | | |
| | Overall dimensions of the transformer and relevant electrical clearances. This shall include all perspectives and respective: | | |
| | a) Weight of oil | | |
| | b) Weight of LV winding conductor | | |
| | c) Weight of HV winding conductor | | |
| | - d) Core material | | |
| | e) Copper winding material | | |
| | f) Insulating material | | |
| | g) Steel tank/core clamp structure | | |
| | Core/coil/insulation dimensions, clearances (internal and external) and stacking/coil winding sequence detail | | |
| | Drawing of nameplate to scale | | |
| | Dimensional drawings of bushings, tapchanger and clamps | | |
| | Legend tor all technical engineering drawings with manufacturers name, logo, model number, revision/drawing number and key | | |
| | Detailed drawing of arcing horns | | |
| | | | |
| Issued by: Head of Section, Standard development <br> Authorized by: Head of Department, Standards | | | |
| Signed: $\qquad$ | | | |
| Date: 2023-01-24 | Date: 2023-01-24 | | |
标题:
文件 No.
KP1/13D/13/TSP/10/001-02
配电变压器 第 2 部分:柱装式三相油式配电变压器 - 规格
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
TITLE: Doc. No. KP1/13D/13/TSP/10/001-02
"DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 38 of 50
"
4.3
4.3 .1
4.3 .2
" All design drawings MUST BE stamped and signed by the manufacturer's authorized personnel
Ratings
KVA, no-load voltage ratings and frequency
Temperature Rise Top Oil
Windings
"Winding hot spot and of
with cellulose" metallic part in contact
Temperature Rise Test
4.3 .3 Fault level for 3 seconds
4.3.4 Demonstration of thermal ability of offered transformer design to withstand short circuit (submit detailed calculation in accordance with clause 4.1.2 and 4.1.5 of IEC 60076-5)
Value of symmetrical short-circuit current 1 as per clause 4.1.2 of IEC 60076-5
Duration of the symmetrical short-circuit current as per clause 4.1.3 of IEC 60076-5
Maximum permissible values of the average temperature of each winding after short circuit as per clause 4.1.4 of IEC 60076-5
Short circuit current density ( A//mm^(2) ) HV winding
Short circuit current density (A/mm ^(2) ) LV winding
Average temperature theta_(1) attained by each winding after short circuit (calculation of temperature as per clause 4.1 .5 of IEC 60076-5)
Issued by: Head of Section, Standard development
Signed: Signed:
Date; 2023-01-24 | | | TITLE: | | | | Doc. No. | | KP1/13D/13/TSP/10/001-02 | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | | DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | | | Issue No . | | 7 | | |
| | | | | | | Revision No. | | 0 | | |
| | | | | | | Date of Issue | | 2023-01-24 | | |
| | | | | | | Page 38 of 50 | | | | |
| <br> 4.3 <br> 4.3 .1 <br> 4.3 .2 <br> <br> <br> <br> | All design drawings MUST BE stamped and signed by the manufacturer's authorized personnel | | | | | | | | | |
| | Ratings | | | | | | | | | |
| | KVA, no-load voltage ratings and frequency | | | | | | | | | |
| | Temperature Rise | | Top Oil | | | | | | | |
| | | | Windings | | | | |
| | | | Winding hot spot and of <br> with cellulose | metallic part in contact | | | |
| | Temperature Rise Test | | | | | | | | | | | | |
| 4.3 .3 | Fault level for 3 seconds | | | | | | | | | | | | |
| 4.3.4 | Demonstration of thermal ability of offered transformer design to withstand short circuit (submit detailed calculation in accordance with clause 4.1.2 and 4.1.5 of IEC 60076-5) | | | | | | | | | |
| | Value of symmetrical short-circuit current 1 as per clause 4.1.2 of IEC 60076-5 | | | | | | | | | |
| | Duration of the symmetrical short-circuit current as per clause 4.1.3 of IEC 60076-5 | | | | | | | | | |
| | Maximum permissible values of the average temperature of each winding after short circuit as per clause 4.1.4 of IEC 60076-5 | | | | | | | | | |
| | Short circuit current density ( $\mathrm{A} / \mathrm{mm}^{2}$ ) HV winding | | | | | | | | | |
| | Short circuit current density (A/mm ${ }^{2}$ ) LV winding | | | | | | | | | |
| | Average temperature $\theta_{1}$ attained by each winding after short circuit (calculation of temperature as per clause 4.1 .5 of IEC 60076-5) | | | | | | | | | |
| | | | | | | | | | | |
| Issued by: Head of Section, Standard development | | | | | | | | | | |
| Signed: | Signed: | | | | | | | | | |
| | | | | Date; 2023-01-24 | | | | | | |
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
问题编号
7
修订编号
0
发行日期
2023-01-24
第 39 页,共 50 页
超负荷运行 2 小时后
连续满负荷运行(指示条款 &\amp;
Overload capacity for 2 hours after
continuous full load run (indicate clause & | | Overload capacity for 2 hours after |
| :--- | :--- |
| continuous full load run (indicate clause $\&$ | |
连续满负荷运行(注明条款和标准)
◻\square
4.3.5
符合 IEC 60076-5 第 4.1.1 至 4.1.5 条要求的详细计算结果
4.3.6
提供变压器承受短路动态效应能力的类型测试报告
◻\square
绕组、绝缘和连接 4.4
Windings, Insulation and connections
4.4| Windings, Insulation and connections |
| :--- |
| 4.4 |
TITLE Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 40 of 50
Aluminum Resistivity at 100^(@)C ( mu ת.m)
Standard of manufacture
Type designation or grade
Specific heat at 100^(@)C (J/kg. ^(0)C )
Density at 100^(0)C(kg//m^(3))
Resistivity at 100^(@)C ( mu Omega.m)
Characteristics of copper foil/strip or aluminum strip in the secondary winding
Copper Standard of manufacture
Type designation or grade
Ultimate tensile strength, N//mm^(2)
Density at 20^(@)C(kg//dm^(3))
Elongation, %, min
Maximum resistance at 20^(@)C,Omegamm^(2)//m
Aluminum Standard of manufacture
Type designation or grade
Ultimate tensile strength, N//mm^(2)
Density at 20^(0)C(kg//dm^(3))
Elongation, %, min
Maximum resistance at 20^(@)C,Omegamm^(2)//m
4.4.3 Insulating materials
Separation of windings for cooling and ease of repair.
Insulation sleeves material
Interlayer insulation material
Issued by: Head of Section, Standard development
"Signed:
Date: 2023-01-24"
Date: 2023-01-24 | | TITLE | | | Doc. No. | KP1/13D/13/TSP/10/001-02 | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | | | | Issue No. | 7 | | |
| | | | | Revision No. | 0 | | |
| | | | | Date of Issue | 2023-01-24 | | |
| | | | | Page 40 of 50 | | | |
| Aluminum | | Resistivity at $100^{\circ} \mathrm{C}$ ( $\mu$ ת.m) | | | | | |
| | | Standard of manufacture | | | | | |
| | | | Type designation or grade | | | | |
| | | Specific heat at $100^{\circ} \mathrm{C}$ (J/kg. ${ }^{0} \mathrm{C}$ ) | | | | | |
| | | Density at $100^{0} \mathrm{C}\left(\mathrm{kg} / \mathrm{m}^{3}\right)$ | | | | | |
| | | | Resistivity at $100^{\circ} \mathrm{C}$ ( $\mu \Omega$.m) | | | | |
| | Characteristics of copper foil/strip or aluminum strip in the secondary winding | | | | | | |
| | Copper | Standard of manufacture | | | | | |
| | | | Type designation or grade | | | | |
| | | | Ultimate tensile strength, $\mathrm{N} / \mathrm{mm}^{2}$ | | | | |
| | | Density at $20^{\circ} \mathrm{C}\left(\mathrm{kg} / \mathrm{dm}^{3}\right)$ | | | | | |
| | | | Elongation, %, min | | | | |
| | | | Maximum resistance at $20^{\circ} \mathrm{C}, \Omega \mathrm{mm}^{2} / \mathrm{m}$ | | | | |
| | Aluminum | Standard of manufacture | | | | | |
| | | Type designation or grade | | | | | |
| | | Ultimate tensile strength, $\mathrm{N} / \mathrm{mm}^{2}$ | | | | | |
| | | Density at $20^{0} \mathrm{C}\left(\mathrm{kg} / \mathrm{dm}^{3}\right)$ | | | | | |
| | | Elongation, %, min | | | | | |
| | | Maximum resistance at $20^{\circ} \mathrm{C}, \Omega \mathrm{mm}^{2} / \mathrm{m}$ | | | | | |
| 4.4.3 | Insulating materials | | | | | | |
| | Separation of windings for cooling and ease of repair. | | | | | | |
| | Insulation sleeves material | | | | | | |
| | Interlayer insulation material | | | | | | |
| | | | | | | | | |
| Issued by: Head of Section, Standard development | | | | | | | |
| Signed: <br> Date: 2023-01-24 | | | | | | | |
| | | Date: 2023-01-24 | | | | | | |
肯尼亚电力公司
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 41 页,共 50 页
Kenya Power "TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 41 of 50 | Kenya Power | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 41 of 50 | |
4.4.3.2
双层绝缘
绝缘温度等级
皱纹纸
制造标准
类型名称或等级
表观密度
克重
水提取物的电导率
油中的电强度
拉伸强度
机器方向
横向机器方向
压纸机纸种
制造标准
类型名称或等级
表观密度
克重
水提取物的电导率
油中的电强度
拉伸强度
机器方向
横向机器方向
牛皮纸/纤维素纸
制造标准
类型名称或等级
表观密度
电导率
透气性
径向垫块
制造标准
类型名称或等级
电气和机械特性
4.4.4
连接
4.4.3.2 Double layer insulation
Temperature class of insulation
Crepe paper Standard of manufacture
Type designation or grade
Apparent density
Grammage
Conductivity of aqueous extract
Electric strength in oil
Tensile strength Machine direction
Cross machine direction
Press paperGrade type Standard of manufacture
Type designation or grade
Apparent density
Grammage
Conductivity of aqueous extract
Electric strength in oil
Tensile strength Machine direction
Cross machine direction
Kraft paper/Cellulos ic paper Standard of manufacture
Type designation or grade
Apparent density
Conductivity
Air permeability
Radial spacer blocks Standard of manufacture
Type designation or grade
Electrical and mechanical properties
4.4.4 Connections | 4.4.3.2 | Double layer insulation | | | | | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | Temperature class of insulation | | | | | | |
| | Crepe paper | Standard of manufacture | | | | | |
| | | Type designation or grade | | | | | |
| | | Apparent density | | | | | |
| | | Grammage | | | | | |
| | | Conductivity of aqueous extract | | | | | |
| | | Electric strength in oil | | | | | |
| | | Tensile strength | Machine direction | | | | |
| | | | Cross machine direction | | | | |
| | Press paperGrade type | Standard of manufacture | | | | | |
| | | Type designation or grade | | | | | |
| | | Apparent density | | | | | |
| | | Grammage | | | | | |
| | | Conductivity of aqueous extract | | | | | |
| | | Electric strength in oil | | | | | |
| | | Tensile strength | Machine direction | | | | |
| | | | Cross machine direction | | | | |
| | Kraft paper/Cellulos ic paper | Standard of manufacture | | | | | |
| | | Type designation or grade | | | | | |
| | | Apparent density | | | | | |
| | | Conductivity | | | | | |
| | | Air permeability | | | | | |
| | Radial spacer blocks | Standard of manufacture | | | | | |
| | | Type designation or grade | | | | | |
| | | Electrical and mechanical properties | | | | | |
| 4.4.4 | Connections | | | | | | |
发布者标准制定科科长
授权人:标准部主任
已签署:
已签署:
日期: 2023-0才-24
日期: 2023-01-24
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: Signed:
Date: 2023-0才-24 Date: 2023-01-24| Issued by: Head of Section, Standard development | Authorized by: Head of Department, Standards |
| :--- | :--- |
| Signed: | Signed: |
| Date: 2023-0才-24 | Date: 2023-01-24 |
标题:
文件 No.
KP1/13D/13/TSP/10/001-02
配电变压器 第 2 部分:柱装式三相油式配电变压器 - 规格
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
TITLE: Doc. No. KP1/13D/13/TSP/10/001-02
"DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 42 of 50
4.4.4.1 Windings, joints & connections braced/brazed? ◻
4.4.4.2 Drying in vacuum & impregnating with hot oil
4.5 Tapping
4.5.1 Tapping range
4.5.2 Tapping method and design
4.5.2.1 Tap changer (ration tapswitch) Standard of manufacture
Type designation or grade
Mode of operation
Shank diameter
Height of ratio tap-switch
Material of external hand wheel and its characteristics that make it long lasting and safe to operate
Locking mechanism to ensure continuous contact onto the selected tapping to avoid open circuit
4.5.2.2 Gap between ratio tap-switch top to the inside of the tank
"4.5.2.3
4.5.2.5" Tap switch position no. lorientation
Make contacts shall be robust and of sufficient surface area as per IEC 60214 and IEC 60512
4.6 Core and Flux Density
4.6.1 Core
Standard of manufacture of core material
4.6.1.1 Type designation or grade of core steel
Insulating material for CRGO to prevent corrosion
4.6.1.2 Thickness of each single lamination
Net core area, mm^(2)
Number of turns on LV, per phase
Stack factor/Building factor
Weight of core, kg
Issued by: Head of Section, Standard development
"Signed:
Date: 2023-01-24" Signed:
Date: 2023-01-24 | | TITLE: | | | | Doc. No. | KP1/13D/13/TSP/10/001-02 | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | | | Issue No. | 7 | | |
| | | | | | Revision No. | 0 | | |
| | | | | | Date of Issue | 2023-01-24 | | |
| | | | | | Page 42 of 50 | | | |
| 4.4.4.1 | Windings, joints & connections braced/brazed? | | | | | | | $\square$ |
| 4.4.4.2 | Drying in vacuum & impregnating with hot oil | | | | | | | |
| 4.5 | Tapping | | | | | | | |
| 4.5.1 | Tapping range | | | | | | | |
| 4.5.2 | Tapping method and design | | | | | | | |
| 4.5.2.1 | Tap changer (ration tapswitch) | Standard of manufacture | | | | | | |
| | | Type designation or grade | | | | | | |
| | | Mode of operation | | | | | | |
| | | Shank diameter | | | | | | |
| | | Height of ratio tap-switch | | | | | | |
| | Material of external hand wheel and its characteristics that make it long lasting and safe to operate | | | | | | | |
| | Locking mechanism to ensure continuous contact onto the selected tapping to avoid open circuit | | | | | | | |
| 4.5.2.2 | Gap between ratio tap-switch top to the inside of the tank | | | | | | | |
| 4.5.2.3 <br> 4.5.2.5 | Tap switch position no. lorientation | | | | | | | |
| | Make contacts shall be robust and of sufficient surface area as per IEC 60214 and IEC 60512 | | | | | | | |
| 4.6 | Core and Flux Density | | | | | | | |
| 4.6.1 | Core | | | | | | | |
| | Standard of manufacture of core material | | | | | | | |
| 4.6.1.1 | Type designation or grade of core steel | | | | | | | |
| | Insulating material for CRGO to prevent corrosion | | | | | | | |
| 4.6.1.2 | Thickness of each single lamination | | | | | | | |
| | Net core area, $\mathrm{mm}^{2}$ | | | | | | | |
| | Number of turns on LV, per phase | | | | | | | |
| | Stack factor/Building factor | | | | | | | |
| | Weight of core, kg | | | | | | | |
| | | | | | | | | |
| Issued by: Head of Section, Standard development | | | | | | | | |
| Signed: <br> Date: 2023-01-24 | | | | Signed: | | | | |
| | | | | Date: 2023-01-24 | | | | |
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
"TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 43 of 50
Specific loss in watts/kg (indicate designed flux density)
4.6.1.3 Static discharges & local heating
4.6.1.4 Assembled core free from distortion
4.6.1.5 Cooling for core
4.6.1.6 Movement of core during transportation or service
4.6.1.7 Core clamping
4.6.1. 8 Lifting lugs for core, winding and complete transformer. Factor of safety at least 2.
4.6.1.9 Oil pockets & trapping of air
4.6.1.10 Insulation withstand of core to bolts and core to frame
4.6 .2 Flux density
4.6.2.1 Effect of primary voltage variations on flux density
4.6.2.2 Maximum working flux density
4.6.2.3 Allowable maximum flux density for one minute and for five seconds
4.6.2.4 Flux density at which core saturates
4.6.2.5 Magnetization curve and design calculations
4.7 Losses
4.7.1 Short-circuit Impendence Voltage, %
4.7 .2 Resistance at 75^(@)C of HV Winding in ohms (at normal & extreme taps)
Resistance at 75^(@)C of LV Winding in ohms
Minimum efficiency at 50% load (unity power factor), at 75^(@)C
Total losses (no-load + load losses) at 50% load
No-load Losses at 75^(@)C
Load Losses at 50% load, 75^(@)C
Load Losses at 75% load, 75^(@)C
Load Losses at 100% load, 75^(@)C
Issued by: Head of Section, Standard development
Signed: Signed:
Date: 2023-01-24 | | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | Doc. No. | KP1/13D/13/TSP/10/001-02 | |
| :--- | :--- | :--- | :--- | :--- | :--- |
| | | | Issue No. | 7 | |
| | | | Revision No. | 0 | |
| | | | Date of Issue | 2023-01-24 | |
| | | | Page 43 of 50 | | |
| Specific loss in watts/kg (indicate designed flux density) | | | | | |
| 4.6.1.3 | Static discharges & local heating | | | | |
| 4.6.1.4 | Assembled core free from distortion | | | | |
| 4.6.1.5 | Cooling for core | | | | |
| 4.6.1.6 | Movement of core during transportation or service | | | | |
| 4.6.1.7 | Core clamping | | | | |
| 4.6.1. 8 | Lifting lugs for core, winding and complete transformer. Factor of safety at least 2. | | | | |
| 4.6.1.9 | Oil pockets & trapping of air | | | | |
| 4.6.1.10 | Insulation withstand of core to bolts and core to frame | | | | |
| 4.6 .2 | Flux density | | | | |
| 4.6.2.1 | Effect of primary voltage variations on flux density | | | | |
| 4.6.2.2 | Maximum working flux density | | | | |
| 4.6.2.3 | Allowable maximum flux density for one minute and for five seconds | | | | |
| 4.6.2.4 | Flux density at which core saturates | | | | |
| 4.6.2.5 | Magnetization curve and design calculations | | | | |
| 4.7 | Losses | | | | |
| 4.7.1 | Short-circuit Impendence Voltage, % | | | | |
| 4.7 .2 | Resistance at $75^{\circ} \mathrm{C}$ of HV Winding in ohms (at normal & extreme taps) | | | | |
| | Resistance at $75^{\circ} \mathrm{C}$ of LV Winding in ohms | | | | |
| | Minimum efficiency at $50 \%$ load (unity power factor), at $75^{\circ} \mathrm{C}$ | | | | |
| | Total losses (no-load + load losses) at 50% load | | | | |
| | No-load Losses at $75^{\circ} \mathrm{C}$ | | | | |
| | Load Losses at $50 \%$ load, $75^{\circ} \mathrm{C}$ | | | | |
| | Load Losses at $75 \%$ load, $75^{\circ} \mathrm{C}$ | | | | |
| | Load Losses at $100 \%$ load, $75^{\circ} \mathrm{C}$ | | | | |
| | | | | | |
| Issued by: Head of Section, Standard development | | | | | |
| Signed: | | | Signed: | | |
| | | | Date: 2023-01-24 | | |
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
"TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 44 of 50
I^(2)R component of load losses at 100% load, 75^(@)C
Load Losses at 125% load, 75^(@)C
Stray Losses at 50% load, 75% load, 100% load and 120% load, all at 75^(@)C
Total losses at maximum tap at 75^(@)C
Total losses at minimum tap at 75^(@)C
4.7 .3 Sound power level
4.7 .4 No-load and Load Losses shall be submitted with tender
4.8 Capitalization
4.9 Bushings and Clearances - - - -
4.9.1.1 Open, outdoor & weatherproof bushings to IEC 60137
4.9.1.2 Bushings to be changed without opening transformer
4.9.1.3 HV bushings to be polymeric or porcelain. Specify
4.9.1.4 HV bushings complete with surge diverters, brackets and arcing horns. Specify
4.9.1.5 LV bushings shall be two part, bottom in toughened epoxy and top in porcelain, brown
HV & LV bushings on top cover
4.9.1.6 LV neutral identical to LV phase terminal bushing
4.9.1.7 Spacing & clearances
4.9.1.8 Creepage distance of bushings: HV, LV, N
4.9.1.9 Clamp type bushing terminals for aluminum conductor
Materials, size and drawings for terminal connectors
4.9.1.10 Marking and method of marking of terminals
Issued by: Head of Section, Standard develop ment
Signed:
Date: 2023-01-24 | | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | | Doc. No. | | KP1/13D/13/TSP/10/001-02 | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | | | | Issue No. | | 7 | | |
| | | | | Revision No. | | 0 | | |
| | | | | Date of Issue | | 2023-01-24 | | |
| | | | | Page 44 of 50 | | | | |
| | $I^{2} \mathrm{R}$ component of load losses at $100 \%$ load, $75^{\circ} \mathrm{C}$ | | | | | | | |
| | Load Losses at $125 \%$ load, $75^{\circ} \mathrm{C}$ | | | | | | | |
| | Stray Losses at 50% load, $75 \%$ load, $100 \%$ load and $120 \%$ load, all at $75^{\circ} \mathrm{C}$ | | | | | | | |
| | Total losses at maximum tap at $75^{\circ} \mathrm{C}$ | | | | | | | |
| | Total losses at minimum tap at $75^{\circ} \mathrm{C}$ | | | | | | | |
| 4.7 .3 | Sound power level | | | | | | | |
| 4.7 .4 | No-load and Load Losses shall be submitted with tender | | | | | | | |
| 4.8 | Capitalization | | | | | | | |
| 4.9 | Bushings and Clearances | | - | | - | | - | - |
| 4.9.1.1 | Open, outdoor & weatherproof bushings to IEC 60137 | | | | | | | |
| 4.9.1.2 | Bushings to be changed without opening transformer | | | | | | | |
| 4.9.1.3 | HV bushings to be polymeric or porcelain. Specify | | | | | | | |
| 4.9.1.4 | HV bushings complete with surge diverters, brackets and arcing horns. Specify | | | | | | | |
| 4.9.1.5 | LV bushings shall be two part, bottom in toughened epoxy and top in porcelain, brown | | | | | | | |
| | HV & LV bushings on top cover | | | | | | | |
| 4.9.1.6 | LV neutral identical to LV phase terminal bushing | | | | | | | |
| 4.9.1.7 | Spacing & clearances | | | | | | | |
| 4.9.1.8 | Creepage distance of bushings: HV, LV, N | | | | | | | |
| 4.9.1.9 | Clamp type bushing terminals for aluminum conductor | | | | | | | |
| | Materials, size and drawings for terminal connectors | | | | | | | |
| 4.9.1.10 | Marking and method of marking of terminals | | | | | | | |
| | | | | | | | | |
| Issued by: Head of Section, Standard develop ment | | | | | | | | |
| Signed: | | | | | | | | |
| Date: 2023-01-24 | | | | | | | | |
标题: 配电变压器 第 2 部分:极装式三相油式配电变压器--规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Polc Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Polc Mounted Three Phase Oil Type Distribution Transformer - Specification |
"TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Polc Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 45 of 50
"4.9.1.11 13
4.10
4.10 .1
4.10.1.1
4.10.1.2" Continuous current rating of each bushing and material of bushing rod and size
Clearances - - - -
External Air Clearances
Adequate to withstand impulse test voltages
Position of fittings and accessorics not to interfere with external connections to bushing terminals
Minimum External clearances
LV, mm Phase to phase
Phase to earth
Creepage distance
11kV,mm Phase to phase
Phase to earth
Creepage distance
33 kV , mm Phase to phase
Phase to earth
Creepage distance
4.10 .2 Internal clearances
Minimum radial clearance of LV coil and core, mm
Minimum radial clearance of LV coil and earth, mm
Minimum radial clearance between LV and HV, mm
Minimum electrical clearance between the surface of the tank and tapping leads, mm
Minimum radial clearance between HV and HV windings, mm
4.11 Insulation Levels (internal)
11 kV : Lightning impulse and power frequency withstand voltage
33 kV : Lightning impulse and power frequency withstand voltage
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
"Signed:
Signed:"
Date: 2023-01-24 Date: 2023-01-24 | | | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Polc Mounted Three Phase Oil Type Distribution Transformer - Specification | | | Doc. No. | | KP1/13D/13/TSP/10/001-02 | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | | | | | Issue No . | | 7 | | |
| | | | | | Revision No. | | 0 | | |
| | | | | | Date of Issue | | 2023-01-24 | | |
| | | | | | Page 45 of 50 | | | | |
| 4.9.1.11 13 <br> 4.10 <br> 4.10 .1 <br> 4.10.1.1 <br> 4.10.1.2 | Continuous current rating of each bushing and material of bushing rod and size | | | | | | | | |
| | Clearances | | | - | | - | | - | - |
| | External Air Clearances | | | | | | | | |
| | Adequate to withstand impulse test voltages | | | | | | | | |
| | Position of fittings and accessorics not to interfere with external connections to bushing terminals | | | | | | | | |
| | Minimum External clearances | | | | | | | | |
| | LV, mm | Phase to phase | | | | | | | |
| | | Phase to earth | | | | | | | |
| | | Creepage distance | | | | | | | |
| | $11 \mathrm{kV}, \mathrm{mm}$ | Phase to phase | | | | | | | |
| | | Phase to earth | | | | | | | |
| | | Creepage distance | | | | | | | |
| | 33 kV , mm | Phase to phase | | | | | | | |
| | | Phase to earth | | | | | | | |
| | | Creepage distance | | | | | | | |
| 4.10 .2 | Internal clearances | | | | | | | | |
| | Minimum radial clearance of LV coil and core, mm | | | | | | | | |
| | Minimum radial clearance of LV coil and earth, mm | | | | | | | | |
| | Minimum radial clearance between LV and HV, mm | | | | | | | | |
| | Minimum electrical clearance between the surface of the tank and tapping leads, mm | | | | | | | | |
| | Minimum radial clearance between HV and HV windings, mm | | | | | | | | |
| 4.11 | Insulation Levels (internal) | | | | | | | | |
| | 11 kV : Lightning impulse and power frequency withstand voltage | | | | | | | | |
| | 33 kV : Lightning impulse and power frequency withstand voltage | | | | | | | | |
| Issued by: Head of Section, Standard development | | | | Authorized by: Head of Department, Standards | | | | | |
| Signed: <br> Signed: | | | | | | | | | |
| Date: 2023-01-24 | Date: 2023-01-24 | | | | | | | | |
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器--规格
TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification| TITLE: DISTRIBUTION TRANSFORMERS |
| :--- |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification |
"TITLE: DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 47 of 50
"4.16.1 (c)
4.16 .1 (d)" Earthing Terminals: location & to have stainless steel bolts, nuts and washers ◻
Separate Lifting lugs for core, top cover & complete transformer
4.16 .1 (e) ◻
"4.16 .1 (f)
4.16 .1 (h)
4.16.1 (j)" Tinned copper jumper size and materials
4.16.1(g) Rating and diagram plate
Clamp Connectors
Surge arrester mounting brackets Mounting brackets dimensions
Universal type
Galvanized to ISO 1461
Surge arrester earthing connection Flexible corrosion proof braided wire capable of withstanding 10 kA https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-47.jpg?height=86&width=666&top_left_y=1299&top_left_x=1207 ◻ https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-47.jpg?height=31&width=33&top_left_y=1315&top_left_x=1854
Arcing Horns provided on HV bushings. State material and arcing gap distance
4.16 .2 Features to deter oil vandalism
4.16 .3 Detailed drawings https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-47.jpg?height=51&width=483&top_left_y=1496&top_left_x=1207
4.16 .4 Transformer mounting rail at bottom ◻
5 Marking, Labeling & Packing
"5.2
5.3" Dispatch fully assembled and oil filled and complete with surge arrester mounting brackets
Assemble & package of items suitably marked https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-47.jpg?height=97&width=36&top_left_y=1900&top_left_x=1833
5.4 Permanent rating and Diagram plate indelibly marked (by etching, engraving or stamping)
5.5 Content of marking
Issued by: Head of Section, Standard development
Signed:
Date: 2023-01-24 | | TITLE: DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transformer - Specification | | Doc. No. | KP1/13D/13/TSP/10/001-02 | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | | | Issue No. | 7 | | |
| | | | Revision No. | 0 | | |
| | | | Date of Issue | 2023-01-24 | | |
| | | | Page 47 of 50 | | | |
| 4.16.1 (c) <br> 4.16 .1 (d) | Earthing Terminals: location & to have stainless steel bolts, nuts and washers | | $\square$ | | | |
| | Separate Lifting lugs for core, top cover & complete transformer | | | | | |
| 4.16 .1 (e) | | | $\square$ | | | |
| 4.16 .1 (f) <br> 4.16 .1 (h) <br> 4.16.1 (j) | Tinned copper jumper size and materials | | | | | |
| | $4.16 .1(\mathrm{~g})$ Rating and diagram plate | | | | | | |
| | Clamp Connectors | | | | | |
| | Surge arrester mounting brackets | Mounting brackets dimensions | | | | |
| | | Universal type | | | | |
| | | Galvanized to ISO 1461 | | | | |
| | Surge arrester earthing connection | Flexible corrosion proof braided wire capable of withstanding 10 kA |  | | $\square$ |  |
| | Arcing Horns provided on HV bushings. State material and arcing gap distance | | | | | |
| 4.16 .2 | Features to deter oil vandalism | | | | | |
| 4.16 .3 | Detailed drawings | |  | | | |
| 4.16 .4 | Transformer mounting rail at bottom | | | | $\square$ | |
| 5 | Marking, Labeling & Packing | | | | | |
| | | | | | | |
| | | | | |
| | | | | | | | |
| 5.2 <br> 5.3 | Dispatch fully assembled and oil filled and complete with surge arrester mounting brackets | | | | | | | | |
| | Assemble & package of items suitably marked | | | | |  |
| 5.4 | Permanent rating and Diagram plate indelibly marked (by etching, engraving or stamping) | | | | | |
| 5.5 | Content of marking | | | | | |
| | | | | | | |
| Issued by: Head of Section, Standard development | | | | | | |
| Signed: | | | | | | |
| | Date: 2023-01-24 | | | | | |
标题: 配电变压器 第 2 部分:杆装三相油式配电变压器 - 规格
TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonmer - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonmer - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
Issue No.
7
修订编号
0
发行日期
2023-01-24
第 48 页,共 50 页
附录 A
测试和检查
-
-
-
-
测试标准
测试变压器的责任和制造商进行指定测试的能力
符合 IEC 60076 标准的型式试验报告副本
雷电冲击耐受测试
短路耐压测试
温升测试
KPLC 工程师应在生产过程中对原材料和每种尺寸的随机样本进行阶段检查
提供原材料检验证书以及采购和支付相关税费的证明文件
A.4
在制造商处所进行验收测试
A.4.1
常规测试符合 IEC 60076 标准
◻\square
A.4.2
符合 IEC 60076 标准的型式试验副本
◻\square
◻\square
◻\square
◻\square
◻\square
90%90 \% 和 110%110 \% 额定电压下的无负载损耗和电流
◻\square
A.4.3
附加测试(样本测试)
◻\square
按照 IEC 60410 标准取样
◻\square
A.5
为核查遵守情况而取消一个单位的油箱
A.6
检测机构的联系方式
A.7
在装运前完成测试报告供审批
◻\square
◻\square
A.8
肯尼亚电力公司在交货时进行检查或测试,然后再验收入库
附录
-
-
-
-
-| - |
| :--- |
| - |
印发日期标准制定科科长
授权人:标准部主任
已签署:
日期: 2023-01-24
日期: 2023-01-24
"TITLE:
DISTRIBUTION TRANSFORMERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonmer - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
lssue No . 7
Revision No. 0
Date of Issue 2023-01-24
Page 48 of 50
Appendix A Tests and Inspection - - - -
Test Standard
Responsibility of testing transformer & manufacturer's capability to carry out specified tests
Copies of type test reports to IEC 60076
Lightning impulse withstand test
Short circuit withstand test
Temperature rise test
KPLC Engineers shall conduct stage inspections on raw materials and random samples of each size during manufacture
Furnish raw materials test certificates as well as documentary proof of purchase and payment of relevant taxes/duty
A. 4 Acceptance tests at manufacturers premises
A.4.1 Routine tests to IEC 60076 ◻
A.4.2 Copies of Type tests to IEC 60076 ◻
https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-48.jpg?height=236&width=655&top_left_y=1495&top_left_x=502 ◻
◻ ◻
◻
No load loss and current at 90% and 110% rated voltage ◻
A.4.3 Additional tests (sample test) ◻
Sampling as per IEC 60410 ◻
A. 5 Untanking of one unit for compliance verification
A. 6 Contact details for testing authority
A. 7 Complete test reports for approval before shipment ◻ ◻
A. 8 Inspection or test by Kenya Power during delivery before acceptance to stores
Appendix - "-
-"
Issued lyy: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed:
Date: 2023-01-24 Date: 2023-01-24 | | TITLE: <br> DISTRIBUTION TRANSFORMERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonmer - Specification | | | | Doc. No. | | | KP1/13D/13/TSP/10/001-02 | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | | | | | lssue No . | | | 7 | | |
| | | | | | Revision No. | | | 0 | | |
| | | | | | Date of Issue | | | 2023-01-24 | | |
| | | | | | Page 48 of 50 | | | | | |
| Appendix A | Tests and Inspection | | | - | | | - | | - | - |
| | Test Standard | | | | | | | | | |
| | Responsibility of testing transformer & manufacturer's capability to carry out specified tests | | | | | | | | | |
| | Copies of type test reports to IEC 60076 | | | | | | | | | |
| | Lightning impulse withstand test | | | | | | | | | |
| | Short circuit withstand test | | | | | | | | | |
| | Temperature rise test | | | | | | | | | |
| | KPLC Engineers shall conduct stage inspections on raw materials and random samples of each size during manufacture | | | | | | | | | |
| | Furnish raw materials test certificates as well as documentary proof of purchase and payment of relevant taxes/duty | | | | | | | | | |
| A. 4 | Acceptance tests at manufacturers premises | | | | | | | | | |
| A.4.1 | Routine tests to IEC 60076 | | | | | | | | | $\square$ |
| A.4.2 | Copies of Type tests to IEC 60076 | | | | | | | | | $\square$ |
| |  | | | | | | | | | | $\square$ |
| | | | | | $\square$ | | | | | | $\square$ |
| | | | | | | | | | | | $\square$ |
| | | | | | No load loss and current at $90 \%$ and $110 \%$ rated voltage | | | | | | | | | $\square$ |
| A.4.3 | Additional tests (sample test) | | | | | | | | | $\square$ |
| | Sampling as per IEC 60410 | | | | | | | | | $\square$ |
| A. 5 | Untanking of one unit for compliance verification | | | | | | | | | |
| A. 6 | Contact details for testing authority | | | | | | | | | |
| A. 7 | Complete test reports for approval before shipment | | | | | | | | $\square$ | $\square$ |
| A. 8 | Inspection or test by Kenya Power during delivery before acceptance to stores | | | | | | | | | |
| Appendix | | | | - | | | - <br> - | | | |
| Issued lyy: Head of Section, Standard development | | | Authorized by: Head of Department, Standards | | | | | | | |
| | Signed: | | | | | | | | | |
| Date: 2023-01-24 | Date: 2023-01-24 | | | | | | | | | |
标题: 配电变流器 第 2 部分:杆装三相油式配电变流器 - 规格
TITLE:
DISTRIBUTION TRANSFORMIERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonner - Specification| TITLE: |
| :--- |
| DISTRIBUTION TRANSFORMIERS |
| Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonner - Specification |
文件 No.
KP1/13D/13/TSP/10/001-02
问题编号
7
修订编号
0
发行日期
2023-01-24
第 49 页,共 50 页
150-\begin{array}{r}150 \\ -\quad \\ \hline\end{array} 提交的 ISO 9001:2015 证书副本
150-
Copy of ISO 9001:2015 certificate submitted| $\begin{array}{r}150 \\ -\quad \\ \hline\end{array}$ |
| :--- |
| Copy of ISO 9001:2015 certificate submitted |
◻\square ◻\square
附录 C
技术文档
◻\square
C.1
投标书连同所有技术文件一并提交
C.2
中标者须在生产前提交文件/细节供批准
C.3
所有关键原材料供应商的完整清单
◻\square
◻\square
其他 完整变压器的重量(千克
◻\square
◻\square
详细信息 罐体重量(千克
details
Weight of tank, kg| details |
| :--- |
| Weight of tank, kg |
◻\square
◻\square
水箱材料
投标书要求
油重量(千克
核心重量(千克
绕组重量(无绝缘),千克
隔热材料重量(千克
导体面积(单位: cm^(2)\mathrm{cm}^{2} ),用于高压和低压绕组
电流密度(安培) //cm^(2)/ \mathrm{cm}^{2} ,用于高压和低压绕组
客户推荐表和四封推荐信
制造商的经验
制造商的生产能力(月产量)
制造商保修和担保
制造商和数量
发布者标准制定科科长
qquad\qquad
已签署:
日期: 2023-01-24
日期: 2023-01-24
"TITLE:
DISTRIBUTION TRANSFORMIERS
Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonner - Specification" Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 49 of 50
"150-
Copy of ISO 9001:2015 certificate submitted" ◻◻
https://cdn.mathpix.com/cropped/2025_05_06_92deb149bb66fc546757g-49.jpg?height=47&width=167&top_left_y=597&top_left_x=1704
Appendix C Technical Documentation ◻
C. 1 Tender submitted with all technical documents
C. 2 Successful bidder to submit documents/details for approval before manufacture
C. 3 Full list of all their vendors of critical raw materials ◻ ◻
Other Weight of complete transformer, kg ◻ ◻
"details
Weight of tank, kg" ◻ ◻
Material of tank
required with the tender Weight of oil, kg
Weight of core, kg
Weight of windings (without insulation), kg
Weight of insulation, kg
Conductor area in cm^(2), indicate for HV and LV windings
Current density in Amps //cm^(2), indicate for HV and LV windings
Customer reference list and four reference letters
Manufacturer's experience
Manufacturer's capacity (number of units per month)
Manufacturer's warranty and guarantee
manufacturer and quantities
Issued by: Head of Section, Standard development
qquad Signed:
Date: 2023-01-24 Date: 2023-01-24 | | | TITLE: <br> DISTRIBUTION TRANSFORMIERS <br> Part 2: Pole Mounted Three Phase Oil Type Distribution Transfonner - Specification | Doc. No. | KP1/13D/13/TSP/10/001-02 | | |
| :--- | :--- | :--- | :--- | :--- | :--- | :--- |
| | | | Issue No. | 7 | | |
| | | | Revision No. | 0 | | |
| | | | Date of Issue | 2023-01-24 | | |
| | | | Page 49 of 50 | | | |
| $\begin{array}{r}150 \\ -\quad \\ \hline\end{array}$ <br> Copy of ISO 9001:2015 certificate submitted | | | | | $\square$$\square$ | |
| | | | | | |  |
| | | | | | | |
| Appendix C | Technical Documentation | | | | | $\square$ |
| C. 1 | Tender submitted with all technical documents | | | | | |
| C. 2 | Successful bidder to submit documents/details for approval before manufacture | | | | | |
| C. 3 | Full list of all their vendors of critical raw materials | | | | $\square$ | $\square$ |
| Other Weight of complete transformer, kg | | | | | $\square$ | $\square$ |
| details <br> Weight of tank, kg | | | | | $\square$ | $\square$ |
| Material of tank | | | | | | |
| required with the tender | Weight of oil, kg | | | | | |
| | Weight of core, kg | | | | | |
| | Weight of windings (without insulation), kg | | | | | |
| | Weight of insulation, kg | | | | | |
| | Conductor area in $\mathrm{cm}^{2}$, indicate for HV and LV windings | | | | | |
| | Current density in Amps $/ \mathrm{cm}^{2}$, indicate for HV and LV windings | | | | | |
| | Customer reference list and four reference letters | | | | | |
| | Manufacturer's experience | | | | | |
| | Manufacturer's capacity (number of units per month) | | | | | |
| | Manufacturer's warranty and guarantee | | | | | |
| | manufacturer and quantities | | | | | |
| | | | | | | |
| Issued by: Head of Section, Standard development | | | | | | |
| $\qquad$ | | | Signed: | | | |
| Date: 2023-01-24 | Date: 2023-01-24 | | | | | |
List catalogues, brochures and technical data submitted to support offer
Deviations from tender specifications (indicate supporting documents submitted)
Manufacturer's Name, Signature, Stamp and Date| List catalogues, brochures and technical data submitted to support offer |
| :--- |
| Deviations from tender specifications (indicate supporting documents submitted) |
| Manufacturer's Name, Signature, Stamp and Date |
发布者标准制定科科长
授权人:标准部主任
已签署:
◯C_(5)\bigcirc C_{5}
日期;2023-01-24
Kenya Power TITLE: Doc. No. KP1/13D/13/TSP/10/001-02
Issue No. 7
Revision No. 0
Date of Issue 2023-01-24
Page 50 of 50
"List catalogues, brochures and technical data submitted to support offer
Deviations from tender specifications (indicate supporting documents submitted)
Manufacturer's Name, Signature, Stamp and Date"
Issued by: Head of Section, Standard development Authorized by: Head of Department, Standards
Signed: ◯C_(5)
Date; 2023-01-24 | Kenya Power | TITLE: | Doc. No. | KP1/13D/13/TSP/10/001-02 |
| :--- | :--- | :--- | :--- |
| | | Issue No. | 7 |
| | | Revision No. | 0 |
| | | Date of Issue | 2023-01-24 |
| | | Page 50 of 50 | |
| List catalogues, brochures and technical data submitted to support offer <br> Deviations from tender specifications (indicate supporting documents submitted) <br> Manufacturer's Name, Signature, Stamp and Date | | | |
| | | | |
| | | | |
| Issued by: Head of Section, Standard development | | Authorized by: Head of Department, Standards | |
| Signed: | | $\bigcirc C_{5}$ | |
| Date; 2023-01-24 | | | |